CJX2 Contactor

Scope of Application
CJX2 Contactor is mainly used for the circuit of AC 50Hz (or 60Hz), the voltage to 660V, the rated operating current to 95A in the utilization category of AC-3, 400V (380V), for the remote on and off circuit, frequent start and control AC motor, and combine with the appropriate thermal relay to form electromagnetic starter to protect the circuit may occur overload operation.
Normal operating conditions and installation conditions
1. Ambient air temperature: -5℃~+40℃, the average does not exceed +35℃ within 24 hours.
2. Altitude: not more than 2000m.
3. Atmospheric conditions: the maximum temperature is +40℃, the relative humidity is not more than 50%; at lower temperatures can allow a higher relative humidity, for example, +20℃ up to 90%, special measures should be taken for condensation produced occasionally due to temperature changes.
4. Pollution level: 3.
5. Installation category: Ⅲ.
6. Installation conditions: The inclination of the installation surface and the vertical plane is not more than ±5°.
7. Shock Vibration: The product should be installed and used in the place without significant shaking, shock and vibration.
8. Installation method: Except for screw installation, but also 35mm standard card rail installation. AC operation 40-95 can installed in 35mm or 75mm card rail.
Other supplier products
|
|
ZW32-12 outdoor vacuum circuit breaker |
Product Overview ZW32-12 outdoor vacuum circuit breaker is a three-phase AC 50Hz outdoor high voltage switch equipment, mainly used in the 10kV out... |
|
|
TXCM1LE Molded Case Circuit Breaker |
Scope of Application TXCM1LE Molded Case Circuit Breaker is one of the new breakers which have been designed and developed by the company using int... |
|
|
HG2B In-line Fuse Switch Disconnector |
Scope of application HG2B In-line Fuse Switch Disconnector is suitable for AC rated voltage 660V and below, AC 160A~630A, rated AC frequency 50Hz. ... |
|
|
TSGC2 Three Phase Voltage Regulator |
Product Overview TSGC2 Three Phase Voltage Regulator is made of three single phase contact voltage regulators adopting "Y"-shaped connection; the c... |
|
|
TXC65-63 Miniature Circuit Breaker |
Scope of ApplicationTXC65-63 Circuit Breaker is used for the circuit of AC 50Hz, rated voltage of 110V/230/400V, rated current of 63A to protect ov... |
供应产品
Same products