Smoke Fire Detector Threshold Test Chamber

Whats/App: +86 156 1874 6768

Web: standard-groups.com

Standards

The system conforms to the following national and international standards:

GB 4715-2005 – Technical Requirements and Test Methods for Point-Type Smoke Fire Detectors (China)

ISO 7240-7 – Fire Detection and Alarm Systems, Part 7: Smoke Detectors Using Scattered, Transmitted Light, or Ionization

EN 54-7 – Fire Detection and Fire Alarm Systems, Smoke Detectors

UL 268 – Standard for Smoke Detectors for Fire Protective Signaling Systems

EN54-7

EN54-29

EN14604

EN54-5

Parameters

UnitSpecification
Temperature Range 0–55 °C, adjustable via heating rods
Variable Frequency Fan Supply voltage: 220 V; Max. static pressure: 330 Pa; Adjustable air volume: 0–275 m³/h
Airflow Requirement 0.2 m/s
Optical Density Meter Wavelength: 880–950 nm
Omega K-Type Sheathed Thermocouple Diameter: 1.5 mm; Temperature measurement range: 0–1100 °C

Features

Steel structure chamber with anti-rust spray finish.

Observation glass on the chamber for visual monitoring of smoke distribution.

Independent control box for flexible laboratory layout.

Fan connected with soft couplings to reduce vibration impact on test data.

Equipped with an ion concentration meter to test the response threshold of ionization detectors.

Flash device included to simulate environmental lighting conditions.

Siemens dedicated temperature module for stable and reliable temperature data acquisition.

Imported Omega thermocouple with compensation wiring reduces temperature measurement deviations.

Programmable logic controller (PLC) enables system function control, paired with dedicated data acquisition modules.

Real-time data acquisition ensures stability and reliability.

Electrical components from reputable industry brands, controlled via industrial PC with dedicated software for real-time recording, storage, and visualization of test data.

Accessories

Observation glass

Variable frequency fan assembly

Heating rod modules

Optical density meter

Ion concentration meter

Flash simulation device

Omega K-type thermocouple and compensation wiring

Siemens temperature acquisition module

PLC controller with data acquisition modules

Industrial PC and dedicated software

Test Procedures

Install the smoke fire detector into the test chamber.

Power on the chamber and set the target temperature within 0–55 °C.

Activate the variable frequency fan and adjust airflow to 0.2 m/s.

Initiate the smoke generation process and monitor optical density readings.

Conduct threshold, repeatability, orientation, and airflow tests according to GB 4715-2005 protocols.

Use ion concentration meter to verify ionization detector response, if applicable.

Apply flash simulation to assess detector response under different lighting conditions.

Record all data in real time using the industrial PC and dedicated software for analysis.

Maintenance Information

Inspect heating rods and replace if temperature control is unstable.

Regularly clean or replace optical density meters and ion concentration sensors to maintain accuracy.

Check fan soft coupling connections to prevent vibration-related errors.

Verify thermocouple calibration periodically to reduce measurement deviations.

Ensure PLC, data acquisition modules, and industrial PC function correctly; perform software updates as required.

Clean observation glass to maintain clear visibility during tests.


Send product request

To: Standard International Group (HK) Limited
Your E-mail:
Message text:


Send to other suppliers

Other supplier products

Solid Combustion Rate Tester
Solid Combustion Rate Tester Whats/App: +86 156 1874 6768 Web: standard-groups.com This product complies with "Recommendations on the Transport of Dangerous Goods - Manual of...
Camera Air Tightness Tester
Camera Air Tightness Tester Whats/App: +86 156 1874 6768 Web: standard-groups.com The Camera Air Tightness Tester is a precision testing instrument used to evaluate the seal...
Fabric Wrinkle Bending Tester | ASTM D1388 Textile Stiffness Testing Machine Manufacturer
Fabric Wrinkle Bending Tester | ASTM D1388 Textile Stiffness Testing Machine Manufacturer Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com Standards The testing methods and results should comply with relevant nation...
ASTM E84 Steiner Tunnel Test Furnace | Flame Spread & Smoke Density Fire Test Equipment Manufacturer
ASTM E84 Steiner Tunnel Test Furnace | Flame Spread & Smoke Density Fire Test Equipment Manufacturer Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com Parameters ParameterSpecification Test Method ASTM E84 / NFPA 25...
Catheter Vacuum Leak Tester
Catheter Vacuum Leak Tester Whats/App: +86 156 1874 6768 Web: standard-groups.com The Catheter Vacuum Leak Tester is a professional device used to detect leaks in medical ca...
All supplier products

Same products

Laser Cutting Machines
Laser Cutting Machines Seller: Chanxan (Changshu) Laser Technology Co., Ltd. Laser Cutting Machines PrecisionLaser Cutting Systemsfor Film, Glass & Industrial Materials ...
Precision Laser Micromachining Machine
Precision Laser Micromachining Machine Seller: Chanxan (Changshu) Laser Technology Co., Ltd. Precision Laser Micromachining Machine| Ultrafast Laser Micromachining Systems Chanxan provides ...
Ultrafast Laser Systems
Ultrafast Laser Systems Seller: Chanxan (Changshu) Laser Technology Co., Ltd. Ultrafast Laser Systems Femtosecond Laser System Ultra-precision femtosecond laser systemfor hi...
Industrial Laser Equipment Manufacturer
Industrial Laser Equipment Manufacturer Seller: Chanxan (Changshu) Laser Technology Co., Ltd. Industrial Laser Equipment Manufacturer for Precision Cutting, Marking & Micromachining Chan...
Common Rail Injector Valve F00R J02 012
Common Rail Injector Valve F00R J02 012 Seller: 868983 Common Rail Injector Valve F00R J02 012 David Chen