Fire-Resistance Cable Burning Test Apparatus,Accurate Fireproof Measurement for Wire Insulation

Whats/App: +86 156 1874 6768

Web: standard-groups.com

The Fire-Resistance Cable Burning Test Apparatus (Cable Fire Integrity Tester) is designed to evaluate the ability of mineral-insulated cables and cables with fire-resistant layers to maintain circuit integrity under flame exposure. The apparatus subjects the test sample to a controlled gas flame under specified temperature, time, and electrical loading conditions, monitoring for short circuits or open circuits. This allows assessment of the cable’s fire-resistance performance. The system is suitable for type tests, factory inspections, and research verification of fire-resistant cables.

Applications

Based on practical applications of domestic and international fire-resistant and flame-retardant cable testing equipment, this apparatus is suitable for the following products and scenarios:

Mineral-insulated cables (MI cables)

Power cables with fire-resistant layer structures

Fire-resistant building wires

Low-voltage control and signal cables

Fire-resistant optical fibers and composite cables

Fire-resistant cables rated ≤ 450/750 V

Verification of fire, flame-retardant, and water-resistant fire performance

Applicable users include cable manufacturers, electrical inspection agencies, fire safety product testing centers, research institutes, and third-party laboratories.

Standards

The apparatus is designed to comply with and support the following standards:

GB/T 19216-2008 — Test methods for cable or optical fiber circuit integrity under flame conditions

GB/T 19666-2019 — General requirements for flame-retardant and fire-resistant wires and cables

IEC 60331-2009 — Tests on electric cables under fire conditions

BS 6387 — Performance requirements for maintaining circuit integrity of cables under fire conditions

BS 8491 — Assessment methods for fire-resistance of cables

Technical Specifications

ItemTechnical Specification
Test Station Single station (one sample at a time)
Sample Length ≥1200 mm
Burner Type Ribbon propane burner with Venturi mixer
Burner Nominal Length 500 mm
Gas Flow Rate 0–50 L/min (adjustable)
Gas Flow Accuracy ±0.1 L/min
Air Flow Rate 0–200 L/min (adjustable)
Air Flow Accuracy ±5 L/min
Flame Temperature Range 450–950 °C (adjustable)
Temperature Sensors K-type stainless steel thermocouples ×2
Thermocouple Max Temperature ≤1100 °C
Control Method PLC + touchscreen operation
Power Consumption 3 kW
Power Supply AC 380 V ±10%, 50 Hz, three-phase five-wire
Gas Supply Propane / LPG + compressed air

Product Features

Mass flow controllers enable high-precision closed-loop control of gas and air flow.

Wide flame temperature adjustment range meets different fire-resistance test requirements.

Circuit integrity detection via breaker replaces traditional fuse structures, improving maintenance efficiency.

Continuous live monitoring system detects open or short circuits in real-time.

Side-mounted exhaust system ensures stable oxygen levels during combustion.

PLC + touchscreen control allows intuitive parameter settings and excellent test repeatability.

Compatible with multiple fire-resistance test modes, including water-spray fire-resistance and mechanical impact tests.

Accessories and Consumables

CategoryNameDescription
Standard Configuration Tubular gas burner Suitable for fire-resistance and water-spray fire tests
Mass flow controller Precision control of gas and air
K-type thermocouple Temperature monitoring
Continuous monitoring device Includes transformer and indicator lights
Exhaust assembly Rapid exhaust of combustion gases
Optional Water-spray fire device Complies with BS 6387 W-class
Mechanical impact device Complies with BS 6387 Z-class
Consumables Gas Propane or LPG
Test cable Test specimen
Seals Periodic replacement required

Testing Principle

During the test, the mass flow controller precisely adjusts the gas-to-air ratio, producing a stable and controllable high-temperature flame. The test cable is subjected to continuous flame while all cores are energized at rated voltage and a load current close to 0.1 A.

A continuous monitoring system observes the circuit status in real-time. Any short-circuit or open-circuit condition triggers an immediate signal, allowing evaluation of whether the sample maintains circuit integrity under the specified flame and loading conditions.

Operation Instructions

Ensure all gas lines, air lines, and exhaust systems are properly connected before testing.

Set the gas flow, air flow, and test duration according to the relevant standard.

Activate the exhaust system before ignition to ensure combustion gases are removed.

Do not open the test chamber door during testing.

For water-spray or water-jet fire tests, calibrate the flow meters and verify the tray setup before ignition.


Send product request

To: Standard International Group (HK) Limited
Your E-mail:
Message text:


Send to other suppliers

Other supplier products

Drawer slide durability tester
Drawer slide durability tester Whats/App: +86 156 1874 6768 Web: standard-groups.com Product Introduction Drawer slides are fundamental components in furniture, cabinetry, and...
Bag lifting fatigue testing machine
Bag lifting fatigue testing machine Whats/App: +86 156 1874 6768 Web: standard-groups.com This machine is suitable for up and down vibration fatigue test of plastic handbag, garbage...
Photovoltaic module outdoor exposure test system
Photovoltaic module outdoor exposure test system Whats/App: +86 156 1874 6768 Web: standard-groups.com The Photovoltaic Module Outdoor Exposure Test System is designed to simulate real-world env...
Helmets Vertical SpacingInfrared - positioning Tester
Helmets Vertical SpacingInfrared - positioning Tester Whats/App: +86 156 1874 6768 Web: standard-groups.com Purpose This measuring instrument is used to measure the vertical spacing and wearing heig...
Multi-Segment Thermal Manikin for Heat Transfer Simulation
Multi-Segment Thermal Manikin for Heat Transfer Simulation Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com Application The Porton-man Thermal Manikin is suitable for a wide range of a...
All supplier products

Same products

Stainless Steel Flux Cored Welding Wire E308T1-1 E308HT1-1 E308LT1-1 Gas Shielded FCAW Wire for 304 Stainless Steel Welding
Stainless Steel Flux Cored Welding Wire E308T1-1 E308HT1-1 E308LT1-1 Gas Shielded FCAW Wire for 304 Stainless Steel Welding Seller: 863048 Product Description stainless steel flux cored wire E308T1-1 E308HT1-1 E308LT1-1,FCAW stainless ...
E317LT1-1 Flux Cored Wire CO2 Stainless Steel 70% Flux Content 1.0/1.2/1.6mm Diameter OEM Customized 1200C Melting Point
E317LT1-1 Flux Cored Wire CO2 Stainless Steel 70% Flux Content 1.0/1.2/1.6mm Diameter OEM Customized 1200C Melting Point Seller: 863048 XUNZHUO STAINLESS STEEL CORED WELDING WIRE E317LT1-1 CLASSIFICATION: There are ones with diamet...
Mini Jewelry Laser Repair System – 60W to 400W Precision Welding
Mini Jewelry Laser Repair System – 60W to 400W Precision Welding Seller: Beijing JCZ Technology Co., Ltd The Mini Jewelry Laser Welding Machineis an advanced mini laser welding system engineered for pre...
Portable Backpack Laser Cleaning Machine – Lightweight, Efficient Rust & Paint Removal
Portable Backpack Laser Cleaning Machine – Lightweight, Efficient Rust & Paint Removal Seller: Beijing JCZ Technology Co., Ltd TheHCP-M SeriesBackpack Laser Cleaning Machinefeatures a compact pulsed fiber laser system, desig...
Suitcase Pulsed Laser Cleaning Machine | Ultra-Portable Handheld Fiber Laser Cleaner
Suitcase Pulsed Laser Cleaning Machine | Ultra-Portable Handheld Fiber Laser Cleaner Seller: Beijing JCZ Technology Co., Ltd The Suitcase Pulsed Laser Cleaning Machineis an ultra-portable, high-precision handheld fiber las...