Laboratory Fire Smoke and Toxic Gas Test Equipment

Whats/App: +86 156 1874 6768

Web: standard-groups.com

Standards

The system complies with the following standards and test methods:

(1) GB/T 19666 – General Rules for Flame-Retardant and Fire-Resistant Wires, Cables or Optical Cables

(2) EN 50305 – Railway Applications – Test Methods for Fire Behaviour of Electric Cables

(3) BS 6853 Annex B – Code of Practice for Fire Precautions in the Design and Construction of Passenger Carrying Trains

(4) ISO 19700 – Controlled Equivalence Ratio Method for the Determination of Toxic Product Yields in Fire Effluents (Steady-State Tube Furnace Method)

(5)ASTM E1678

(6)NFPA 269

Parameters

ItemSpecification
Tube furnace heating length 600 mm
Temperature range 0–1100 °C
Temperature accuracy ±0.1 °C
Quartz tube Heat-resistant quartz, thickness ≥ 2 mm
SO₂ measurement range 0–1000 ppm
SO₂ resolution 1 ppm
SO₂ accuracy ±30 ppm
NOₓ measurement range 0–3000 ppm
NOₓ resolution 1 ppm
NOₓ accuracy ±30 ppm
Gas sampling bag PTFE-coated, 80 L capacity, with imported manual sampler
CO measurement range 0–10 %
CO resolution 0.01 %
CO accuracy Absolute ±0.1 % or relative ±3 %
CO₂ measurement range 0–20 %
CO₂ resolution 0.01 %
CO₂ accuracy Absolute ±0.2 % or relative ±3 %
Spectral analysis device Spectrometer at 500 nm wavelength, membrane thickness 10 mm
Absorption solution 0.1 N NaOH
Titration reagents Picric acid aqueous solution (3 g/dm³) and sodium carbonate aqueous solution (50 g/dm³)

Features

Sealed chamber design with the smoke generation system installed internally, providing stable operation and effective protection of core components

Large observation window allowing clear visual monitoring of test status and specimen movement

Integrated industrial design with panel-mounted structure, offering intuitive operation and ergonomic user interface

Tube furnace protected by perforated outer housing to enhance heat dissipation and ensure uniform temperature rise to the target value

High-temperature K-type thermocouple for accurate measurement of specimen zone temperature

Ceramic combustion boat driven by strong magnetic coupling and transmission mechanism for stable and repeatable specimen delivery into the furnace core

Precision lead-screw transmission system enabling accurate positioning and reliable sealing of the quartz tube, reducing the risk of damage due to manual operation

Dual filtration columns filled with activated carbon and color-changing silica gel for effective carrier gas purification and drying

Branded computer with dedicated control software for automatic test process control

Software-based temperature regulation and stabilization with real-time curve recording, automatic data display, storage, and report generation

Accessories

(1) Heat-resistant quartz tube

(2) Ceramic combustion boat

(3) PTFE-coated gas sampling bag (80 L)

(4) Activated carbon filter column

(5) Color-changing silica gel filter column

(6) K-type thermocouple

(7) Dedicated control software and industrial computer

Test Procedures

1. Pre-Test Preparation

Ensure the tester is installed in a well-ventilated laboratory environment. Verify that the tube furnace, quartz tube, and filtration system are clean and properly assembled. Check that the absorption solution (0.1 N NaOH) and titration reagents are prepared according to specified concentrations. Confirm normal operation of the temperature control system, gas analysis instruments, and data acquisition software.

2. Specimen Loading

Place the prepared test specimen into the ceramic combustion boat. Using the magnetic drive and transmission mechanism, steadily convey the boat into the center of the tube furnace. The lead-screw positioning system ensures accurate alignment and reliable sealing at the quartz tube interface, minimizing gas leakage during the test.

3. Heating and Smoke Generation

Set the target temperature according to the selected standard. The furnace temperature is automatically controlled by the software, with uniform heating achieved through regulated power output. As the specimen undergoes thermal decomposition or combustion, the generated smoke is carried by a controlled gas flow toward the sampling and absorption system.

4. Gas Collection and Analysis

The combustion gases are either introduced into the NaOH absorption solution via bubbling or collected in PTFE-coated gas sampling bags for subsequent analysis. Online infrared gas analyzers continuously measure CO and CO₂ concentrations, while SO₂ and NOₓ are determined using dedicated measurement channels or chemical analysis methods. All test data are automatically recorded and stored by the control software.

Maintenance Information

Regularly inspect the quartz tube, ceramic combustion boat, and furnace interior for residue buildup and clean them as required. Check the condition of the activated carbon and silica gel in the filter columns and replace them when saturation or discoloration is observed. Verify calibration of gas analyzers and temperature sensors according to laboratory quality procedures. Ensure the lead-screw transmission and magnetic drive mechanisms operate smoothly to maintain positioning accuracy.


Send product request

To: Standard International Group (HK) Limited
Your E-mail:
Message text:


Send to other suppliers

Other supplier products

Flame Spread Tester
Flame Spread Tester Whats/App: +86 156 1874 6768 Web: standard-groups.com The tester is used for flame spread test of protective clothing. It is designed and manufac...
Textile Blanket Flammability Tester Complying with 16 CFR Standards
Textile Blanket Flammability Tester Complying with 16 CFR Standards Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com E-mail:info@standard-groups。com Features Stainless steel body design Exter...
UV Curing Machine
UV Curing Machine Whats/App: +86 156 1874 6768 Web: standard-groups.com Description UV is the ultraviolet (Ultra-VioletRay) English abbreviation. Industrial UV wa...
Battery Isothermal Calorimeter
Battery Isothermal Calorimeter Whats/App: +86 156 1874 6768 Web: standard-groups.com Product Description Battery Isothermal Calorimeter is a professional instrument developed ...
OEM luminous afterglow performance testing equipment factory
OEM luminous afterglow performance testing equipment factory Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com Technical Specifications ParameterSpecification Excitation Light ...
All supplier products

Same products

Common Rail Injector Valve F00R J01 334
Common Rail Injector Valve F00R J01 334 Seller: 868983 Common Rail Injector Valve F00R J01 334 Injector Valve Set F00V C01 361 Injector Valve Set F00V...
Common Rail Injector Valve F 00V C01 371
Common Rail Injector Valve F 00V C01 371 Seller: 868983 Common Rail Injector Valve F 00V C01 371 Injector Valve Set F00V C01 310 Injector Valve Set F00...
Common Rail Injector Valve F 00V C01 365
Common Rail Injector Valve F 00V C01 365 Seller: 868983 Common Rail Injector Valve F 00V C01 365 Injector Valve Set F00V C01 303 Injector Valve Set F...
Common Rail Injector Valve F 00V C01 329
Common Rail Injector Valve F 00V C01 329 Seller: 868983 Common Rail Injector Valve F 00V C01 329 Injector Valve Set F00V C01 054 Injector Valve Set F...
Common Rail Injector Valve F 00V C01 325
Common Rail Injector Valve F 00V C01 325 Seller: 868983 Common Rail Injector Valve F 00V C01 325 Injector Valve Set F00V C01 044 Injector Valve Set F...