Smoke Detector Test Tunnel Manufacturer | EN 54 & UL 268 Fire Alarm Testing Equipment
Get a quote:
Whats/App: +86 156 1874 6768
Web: standard-groups.com
E-mail:info@standard-groups。com
Parameters
| Unit | Specification |
|---|---|
| Temperature Range | 0–55 °C, adjustable via heating rods |
| Variable Frequency Fan | Supply voltage: 220 V; Max. static pressure: 330 Pa; Adjustable air volume: 0–275 m³/h |
| Airflow Requirement | 0.2 m/s |
| Optical Density Meter | Wavelength: 880–950 nm |
| Omega K-Type Sheathed Thermocouple | Diameter: 1.5 mm; Temperature measurement range: 0–1100 °C |
Features
Steel structure chamber with anti-rust spray finish.
Observation glass on the chamber for visual monitoring of smoke distribution.
Independent control box for flexible laboratory layout.
Fan connected with soft couplings to reduce vibration impact on test data.
Equipped with an ion concentration meter to test the response threshold of ionization detectors.
Flash device included to simulate environmental lighting conditions.
Siemens dedicated temperature module for stable and reliable temperature data acquisition.
Imported Omega thermocouple with compensation wiring reduces temperature measurement deviations.
Programmable logic controller (PLC) enables system function control, paired with dedicated data acquisition modules.
Real-time data acquisition ensures stability and reliability.
Electrical components from reputable industry brands, controlled via industrial PC with dedicated software for real-time recording, storage, and visualization of test data.
Accessories
Observation glass
Variable frequency fan assembly
Heating rod modules
Optical density meter
Ion concentration meter
Flash simulation device
Omega K-type thermocouple and compensation wiring
Siemens temperature acquisition module
PLC controller with data acquisition modules
Industrial PC and dedicated software
Test Procedures
Install the smoke fire detector into the test chamber.
Power on the chamber and set the target temperature within 0–55 °C.
Activate the variable frequency fan and adjust airflow to 0.2 m/s.
Initiate the smoke generation process and monitor optical density readings.
Conduct threshold, repeatability, orientation, and airflow tests according to GB 4715-2005 protocols.
Use ion concentration meter to verify ionization detector response, if applicable.
Apply flash simulation to assess detector response under different lighting conditions.
Record all data in real time using the industrial PC and dedicated software for analysis.
Отправить запрос, связаться с поставщиком
Другие товары поставщика
| Laboratory continuous load surface performance tester | Whats/App: +86 156 1874 6768 Web: standard-groups.com Application Adhesion strength evaluation of surface coatings Measurement of friction resi... | |
| Advanced Multifunctional Thermal Conductivity Analyzer for Polymers | Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com Standards The instrument is designed and operated in accordance with the fol... | |
| Fabric Fiber Shedding Degree Tester (Friction) Manufacturer Direct Sale | Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com Features Touch screen controller: The number of frictions can be set arbitra... | |
| Cap Torque Tester | Whats/App: +86 156 1874 6768 Web: standard-groups.com A Bottle Cap Torque Tester is a specialized device used to measure the torque applied to ... | |
| Particle Strength Tester | Whats/App: +86 156 1874 6768 Web: standard-groups.com The Particle Strength Tester is a high-precision instrument designed to measure the mechani... |