FWX1 LBS installed on the pole is suitable for rated voltage 12/24/40.5kV, rated current 630A, 50/60Hz Distribution network breaking. The load current or overload current in a power system automatically isolates the faulty sections of the distribution line. Switch with the latest technology electronic controller, manual operation, electric operation, and remote operation. The electronic controller is installed in the stainless steel box and can be used under various climatic conditions. In addition, cable and wireless modems can be installed in the box to realize remote monitoring and control. Simple installation and arrangement on the pole are convenient, quick, and low construction cost.
Characteristics of 15KV SF6 Gas Load Breaker Switch
The switch is made of proven durable, corrosion-resistant material. (304L stainless steel plate for warships), ensure a long service life (30years), and can carry out a series of operations, with the pole top equipment ideal characteristics.
Each switch has been filled with sf6 gas before leaving the factory, sealed treatment. The test was carried out according to IEC60265-1 (1988) GB 3804-1990 standard.
Specification of 15KV SF6 Gas Load Breaker Switch
Products Type |
FWX-15 |
|
Basic Ratings |
||
Maximum System Voltage |
15KV |
|
Rated Continuous Current |
630A |
|
Rated Frequency |
50/60Hz |
|
Short Time Withstand Current |
IKA/sec |
|
Making and Breaking Capacity |
||
Mainly Active LoadCurrent |
630A |
|
Number of Load-break Operations |
400times |
|
Short-circuit Making Current(peak) |
50KA |
Number of Making Operations |
5 times |
Cable Charging Current |
lOA |
Line Charging Current |
lOA |
Closed Loop Circuit Current |
630A |
Transformer Magnetizing Current |
22A |
Power Frequency Withstand Current Test |
|
Wet Condition- 10 sec (Ph- Ph-Eth, Across Interrupters) |
50KV |
DryCondition- I min ( Phase to Phase, Phase to Earth) |
50KV |
Dry Condition - 1 min (Across Interrupter ) |
60KV |
Impulse Withstand Current Test(1.2 x 50 µs) |
Internal Arc Test |
20kA /0.1 sec |
Arc Extinction Medium |
SF6 Gas |
Insulation Medium |
SF6 Gas |
Creepage Distance (Porcelain) |
560mm |
IP Level |
54 |
Operation Performance |
|
Closing/Opening Tin记 |
< O. l sec |
Mechanica l Operations (Guaranteed) |
l OOOO times |
Operating Temperature.1re(*Manual Type) |
-25~+70℃ |
Gas Pressure |
|
Nominal Pressure (kg/cm2 G, at 20°C) |
|
Bursting Pressure (kg/cm2 G) |
4 ~ 6 |
Minimum Gas Pressure (kg/cm2 G) |
|
Leakage Rate (cc/ sec) |
1% |
Other Ratings & Specifications |
|||
Internal Arc Test |
20kA /0.1 sec |
20kA /0.1 sec |
20kA /0.1 sec |
Arc Extinction Medium |
SF6 Gas |
SF6 Gas |
SF6 Gas |
Insulation Medium |
SF6 Gas |
SF6 Gas |
SF6 Gas |
Creepage Distance (Porcelain) |
380mm |
700mm |
1055mm |
Creepage Distance (Silicon) |
780mm |
1200mm |
1550mm |
Dry arcing distance |
≥200mm |
≥ |
≥ |
IP Level |
65 |
65 |
65 |
Operation Performance |
|||
Closing/Opening Time |
<1sec |
<1sec |
<1sec |
Mechanical Operations (Guaranteed) |
10000times |
10000times |
10000times |
Operating Temperature (*Manual Type) |
-25~+70℃ |
-25~+70℃ |
-25~+70℃ |
Gas Pressure |
|||
Nominal Pressure (MPa, at 20°C) |
|||
Bursting Pressure (MPa) |
|
||
Minimum Gas Pressure (MPa) |
|||
Leakage Rate (cc/ sec) |
≤0.5% |
≤0.5% |
≤0.5% |
Voltage sensors |
|||
CT ABC 10P10 5VA |
400:5 |
400:5 |
400:5 |
Incoming side and outgoing side of the voltage sensor |
6 Voltage sensor(built-in) Phase voltage:(24(36)kV/√3)/(3.25V/√3) |
||
Special attention should be paid to the voltage sensor, which must be directly fed by the switch. No additional adjustment circuit can be added to the controller. The voltage signal of the switch into the test line needs to be tested separately. |
Zhuhai GopowerSmart Grid Co., Ltd. is one of the earliest electric power equipment company. We provide 15kv load break switch, 15 kv pole mounted disconnect switchand etc. Want to know more? Please contact us.
Send product request
Other supplier products
24KV Vacuum Circuit Breaker | 24KV Vacuum Circuit Breaker The 24KV breaker switch unit is comprised of three poles, the operating mechanism, and the operating mechanism housing... | |
Pole Top Switches | The pole mounted disconnect switch is a kind of safety switch used on the electric pole to ensure the safety of electricity. Pole top switch's main... | |
24KV Recloser Vacuum Circuit Breaker | 24KV Recloser Vacuum Circuit Breaker The 24KV breaker switch unit is comprised of three poles, the operating mechanism, and the operating mechanis... | |
SF6 Gas 11KV Load Break Switch | The 11kv load break switchis suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and the rated frequency 5... | |
Centralized Type DTU | The centralized DTU adopts high-performance MCU processor, high-speed industrial network communication technology, multi-CPU integration technology... |
Same products
Floral Garden Tools Set | Seller: Dongyang Guorui Industry And Trade Co., Ltd. | Investing in a floral garden tools set not only enhances your gardening experience but also add... | |
Rice Husk Pellet Machine | Seller: Jiangsu Kingwood Industrial Co., Ltd. | ● JWZL-420 is the most popular biomass/woodpellet machine of all the pellet mills offered by Ch... | |
Greece-liquid nitrogen vapor phase storage systems KGSQ | Seller: Henan Tianzhidao Biological Technology Co., Ltd | In today's era of continuous technological progress, with the increasingly high requirements for ... | |
Common Rail Fuel Injector Nozzle L500PBC | Seller: 738347 | Common Rail Fuel Injector Nozzle L500PBC 0 445 110 189 Injector Valve Set 0 445 110 190 Injector... | |
Common Rail Fuel Injector Nozzle F00VX40014 | Seller: 738347 | Common Rail Fuel Injector Nozzle F00VX40014 Common Rail Fuel Injector Nozzle F340 Common Rail ... |