24KV Recloser Vacuum Circuit Breaker24KV Recloser Vacuum Circuit Breaker
24KV Recloser Vacuum Circuit Breaker
The 24KV breaker switch unit is comprised of three poles, the operating mechanism, and the operating mechanism housing. The sequence of the poles is A -B – C or 1 – 2 - 3 (sequence left to right when viewed from the lower terminal side of the recloserswitch unit.
Each 24kv vacuum circuit breakerby GOPOWER is embedded in a solid-insulated pole made of weather-proof cyclo aliphatic epoxy resin. This enables a small design as well as resistance against environmental effects.
Breaker principle and design of 24KV Vacuum Circuit Breaker
ZW32 series 24KV circuit recloser are used in distribution systems. 24kv vacuum circuit breakes are used to make and break normal and fault currents. Breakers are fully equipped with sensors and a controller to provide a means of protection and control. For more pole top switches at bulk price.
In case of a line fault, breakers can break and make currents several times, thus avoiding longer network interruptions due to temporary faults. The manufacture, design, and testing of the vacuum recloser is based on current standards IEC 62271-111:2019
Technical Parameters of 24KV Vacuum Circuit Breaker
|
Products Type |
ZW32-24 |
|
Maximum System Voltage |
24kV |
|
Rated Continuous Current |
630A |
|
Rated Frequency |
50/60Hz |
|
Short Time Withstand Current |
20kA/1sec |
|
Mainly Active Load Current |
630A |
|
Number of Load-break Operations |
30 |
|
Short-circuit Making Current (peak) |
50kA |
|
Number of Making Operations |
5 times |
|
Cable Charging Current |
25A |
|
Line Charging Current |
|
|
Closed Loop Circuit Current |
630A |
|
Transformer Magnetizing Current |
22A |
|
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters |
50kV |
|
DryCondition-1min,Ph- Ph, Phase to Earth |
65kV |
|
Dry Condition - 1 min AcrossInterrupter |
79kV |
|
Phase to Phase, Phase to Earth |
125kV |
|
Across Interrupter |
145kV |
|
Internal Arc Test |
20kA /0.1 sec |
|
Arc Extinction Medium |
vacuum |
|
Insulation Medium |
vacuum |
|
Creepage Distance (Silicon) |
960mm |
|
Dry arcing distance |
200mm≥ |
|
IP Level |
67 |
|
Closing/Opening Time |
<1sec |
|
Mechanical Operations (Guaranteed) |
10000times |
|
Operating Temperature (*Manual Type) |
-25~+70℃ |
As a reliable electric power equipment ltd, we will do our best to meet all the needs of customers.
Send product request
Other supplier products
| 11KV SF6 Gas Load Break Switch | The FWX1-12/630 outdoor SF6 load break switch is suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and t... | |
| Pole Top Switches | The pole mounted disconnect switch is a kind of safety switch used on the electric pole to ensure the safety of electricity. Pole top switch's main... | |
| Centralized Type DTU | BD-163 distribution automation remote terminal (hereinafter referred to as the distribution terminal) is a new generation of power distribution ter... | |
| Recloser Control Box-Feeder Terminal Unit | The feeder terminal unit(FTU) is a new HV switch control device of control cabinet enclosures equipped with both the imported DSP high-speed sampli... | |
| LBS 24KV 630a SF6 Gas Load Break Switch | 24kV SF6 load break switch is a switch equipment for medium voltage switchgear, using SF6 gas as arc extinguishing and insulating medium. Rate volt... |