600/1000V ABC –Aerial Bundled Cables to BS 7870-5 (AL/XLPE)
600/1000V ABC –Aerial Bundled Cables to BS 7870-5 (AL/XLPE)
Application
The aerial bundled cables designed for overhead distribution lines have all conductors made of aluminium 1350 and insulated with XLPE. Phase and neutral cores are laid up in a bundle with a left hand lay. Can be used for fixed installation as overhead power lines up to 1000 V incl.
Standard
BS 7870-5:1999
Construction
CONDUCTOR (FOR EITHER PHASE, NEUTRAL OR STREET LIGHTING) |
The conductors shall be of aluminium 1350 wires and are compacted circular stranded(RM). |
INSULATION |
XLPE. 1, 2 and 3 raised longitudinal ribs on the surface of the cores. The surface of the neutral core should have at least 12 ribs for cross-sections up to 50 mm² and a minimum of 16 ribs for cores above 50 mm². In the case of five core bundles the surface of the protective core should be smooth. |
ASSEMBLY |
2 up to 4 cores of equal cross section are stranded together in left-hand lay, additionally 1 or 2 cores of reduced cross section can be co-stranded. |
Technical Data
Rated voltage |
kV |
0.6/1 |
Test voltage |
Veff kV |
4 |
Laying temperature |
°C |
min. -20 |
Operating temperature |
°C |
-30 ~ +80 |
Conductor temperature |
°C |
max. +80 |
Short-circuit temperature |
°C/s |
max. +130 /5 |
Bending radius (min.) |
|
18 × ø of cable |
Other supplier products
|
P18 RU 0.6/1kV NEK606 Water Blocked Offshore Marine Cables |
P18 RU 0.6/1kV NEK606 Water Blocked Offshore Marine Cables
Applications
TheseP18 RU 0.6/1kV NEK606 Water Blocked Offshore Marinecables are flame ... |
|
FL2XCY Airport Cable |
FL2XCY Airport Cable
Applications
These cables are used as airfield lighting equipment primary cables for the series circuit connecting the Constan... |
|
All Aluminum Alloy Conductor (AAAC) Cables |
All Aluminum Alloy Conductor (AAAC) Cables
Application
AAAC is mainly used as bare overhead transmission cable and as primary and secondary distri... |
|
FLR31Y11Y Airfield Lighting Cables |
FLR31Y11Y Airfield Lighting Cables
Applications
FLR31Y11Y are used as airfield lighting cable for secondary electrical circuits. The cable insulati... |
|
C 33-224 / C33-225 Airport Cable |
Applications
These cables are used as airfield lighting equipment primary cables for the series circuit connecting the Constant Current Regulators ... |
All supplier products
Same products