SG (B) 10 series Non-encapsulated H-class Dry-type Power Transformers,Dry type Power Transformers,hermetically sealed transformers,dry type transformer
SG (B) 10 series Non-encapsulated H-class Dry-type Power Transformers,Dry type Power Transformers,hermetically sealed transformers,dry type transformer
Dry Type Transformer
Product Description
SG (B) 10 series of non-encapsulated H-class dry-type power transformersadopt the special process technology of German (MORA) dry-type transformers to ensure that the products fully meet the requirements such as fire prevention, waterproof ,environmental protection. It is the ideal product for distribution systems and widely used in the subway, shipbuilding, mining, chemical, power companies and personnel-intensive buildings as well as other special requirements of the occasion for safety.
Model and Meaning
SC(B)10 Series Resin-insulated Dry Type Transformer
SG (B) 10 series Non-encapsulated H-class Dry-type Power Transformers
Technical Parameter for6kV, 10kV& 30kVA-2500kVA With Off Circuit Dry Type Transformer
Rated capacity(KVA) |
Voltage Combination |
Connection Group Symbol |
No-load Loss(W) |
Load Loss (W) |
No-load Current (%) |
Short-circuit Impedance(%) |
||||
High Voltage (KV) |
Tapping rangesof High Voltage |
Low Voltage(KV) |
130℃(B)(100℃) |
155℃(F)(120℃) |
180℃(H)(145℃) |
|||||
30 |
±2X2.5%±5% |
Dyn11Yyn0 |
190 |
670 |
710 |
760 |
||||
50 |
270 |
940 |
1000 |
1070 |
||||||
80 |
370 |
1290 |
1380 |
1480 |
||||||
100 |
400 |
1480 |
1570 |
1690 |
||||||
125 |
470 |
1740 |
1850 |
1980 |
||||||
160 |
540 |
2000 |
2130 |
2280 |
||||||
200 |
±2X2.5%±5% |
620 |
2370 |
2530 |
2710 |
|||||
250 |
720 |
2590 |
2760 |
2960 |
||||||
315 |
880 |
3270 |
3470 |
3730 |
||||||
400 |
980 |
3750 |
3990 |
4280 |
||||||
500 |
1150 |
4590 |
4880 |
5230 |
||||||
630 |
1340 |
5530 |
5880 |
6290 |
||||||
630 |
1300 |
5610 |
5960 |
6400 |
||||||
800 |
1520 |
6550 |
6960 |
7460 |
||||||
1000 |
1770 |
7650 |
8130 |
8760 |
||||||
1250 |
2090 |
9100 |
9690 |
10300 |
||||||
1600 |
2450 |
11000 |
11700 |
12500 |
||||||
2000 |
3050 |
13600 |
14400 |
15500 |
||||||
2500 |
3600 |
16100 |
17100 |
18400 |
||||||
1600 |
2450 |
1220 |
12900 |
13900 |
||||||
2000 |
3050 |
15000 |
15900 |
17100 |
||||||
2500 |
3600 |
17700 |
18800 |
20200 |
Notes:The load losses listed in the table are the values of the reference temperature for different insulation systems inparentheses; The load losses under other insulation system temperatures that are not included in the table should be according to their respective reference temperatures, the corresponding calculation is based on the"- 155 ℃(F)" insulation system temperature data.
Notes:The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.
Technical Parameter for20kV& 50kVA-2500kVA With Off CircuitDry Type Transformer
(KVA)Rated capacity |
Voltage Combination |
Connection Group Symbol |
No-load Loss(W) |
Load Loss (W) |
No-load Current (%) |
Short-circuit Impedance(%) |
||||
High Voltage (KV) |
Tapping rangesof High Voltage |
Low Voltage(KV) |
130℃(B)(100℃) |
155℃(F)(120℃) |
180℃(H)(145℃) |
|||||
50 |
202224 |
±2.5%±5%±5%±2×2.5% |
Dyn11Yyn0 |
340 |
1160 |
1230 |
1310 |
|||
100 |
540 |
1870 |
1990 |
2130 |
||||||
160 |
2350 |
2470 |
3460 |
|||||||
200 |
±2X2.5%±5% |
730 |
2770 |
2940 |
3140 |
|||||
250 |
840 |
3220 |
3420 |
3660 |
||||||
315 |
970 |
3850 |
4080 |
4360 |
||||||
400 |
1150 |
4650 |
4840 |
5180 |
||||||
500 |
1350 |
5460 |
5790 |
6190 |
||||||
630 |
1530 |
6450 |
6840 |
7320 |
||||||
800 |
1750 |
7790 |
8260 |
8840 |
||||||
1000 |
2070 |
9220 |
9780 |
10400 |
||||||
1250 |
2380 |
10800 |
11500 |
12300 |
||||||
1600 |
2790 |
13000 |
13800 |
14800 |
||||||
2000 |
3240 |
15400 |
16300 |
17500 |
||||||
2500 |
18200 |
19300 |
20700 |
|||||||
2000 |
3240 |
16800 |
17800 |
19100 |
||||||
2500 |
3870 |
20000 |
21200 |
22700 |
Technical Parameter for35kV& 50kVA-2500kVA With Off CircuitDry Type Transformer
(KVA)Rated capacity |
Voltage Combination |
Connection Group Symbol |
No-load Loss(W) |
Load Loss (W) |
No-load Current (%) |
Short-circuit Impedance(%) |
||||
High Voltage (KV) |
Tapping rangesof High Voltage |
Low Voltage(KV) |
130℃(B)(100℃) |
155℃(F)(120℃) |
180℃(H)(145℃) |
|||||
50 |
±2.5%±5%±5%±2×2.5% |
Dyn11Yyn0 |
450 |
1340 |
1420 |
1520 |
||||
100 |
630 |
1970 |
2090 |
2230 |
||||||
160 |
2650 |
2810 |
3000 |
|||||||
200 |
±2X2.5%±5% |
3130 |
3320 |
3550 |
||||||
250 |
3580 |
3800 |
4060 |
|||||||
315 |
1170 |
4250 |
4510 |
4820 |
||||||
400 |
1370 |
5100 |
5410 |
5790 |
||||||
500 |
1520 |
6270 |
6650 |
7110 |
||||||
630 |
1860 |
7250 |
7690 |
8230 |
||||||
800 |
2160 |
8600 |
9120 |
9760 |
||||||
1000 |
2430 |
9860 |
10400 |
11100 |
||||||
1250 |
2830 |
12000 |
12700 |
13600 |
||||||
1600 |
3240 |
14600 |
15400 |
16500 |
||||||
2000 |
3820 |
17200 |
18200 |
19500 |
||||||
2500 |
Technical Parameterfor SG(B)10 Series Non-encapsulated Class H Dry-type Transformer
Product Model No. |
Connection Group Symbol |
Loss W |
Impedance Voltage(%) |
No-load Current(%) |
Overall Dimension (without enclosure) mm |
Weight(Kg) |
|||||||
No-load Loss R |
145℃Load Loss R(W) |
L |
W |
H |
L1 |
L2 |
d |
f |
|||||
SG10-30/10 |
Y,yn0D,yn11 |
190 |
760 |
4 |
900 |
1180 |
880 |
265 |
220 |
550 |
550 |
420 |
|
SG10-50/10 |
270 |
1070 |
940 |
1180 |
985 |
295 |
220 |
550 |
550 |
450 |
|||
SG10-80/10 |
370 |
1480 |
985 |
1180 |
1055 |
295 |
226 |
550 |
660 |
740 |
|||
SG10-100/10 |
400 |
1690 |
1010 |
1180 |
1135 |
295 |
226 |
660 |
660 |
770 |
|||
SG10-125/10 |
470 |
1980 |
1060 |
1180 |
1175 |
306 |
228 |
660 |
820 |
1005 |
|||
SG10-160/10 |
540 |
2280 |
1120 |
1180 |
1230 |
312 |
228 |
660 |
820 |
1015 |
|||
SG10-200/10 |
620 |
2710 |
1180 |
1230 |
1275 |
312 |
238 |
660 |
820 |
1035 |
|||
SG10-250/10 |
720 |
2960 |
1290 |
1230 |
1330 |
315 |
238 |
660 |
820 |
1155 |
|||
SG10-315/10 |
880 |
3730 |
1320 |
1340 |
1355 |
315 |
240 |
820 |
1070 |
1365 |
|||
SGB10-400/10 |
980 |
4280 |
1350 |
1340 |
1435 |
315 |
240 |
820 |
1070 |
1585 |
|||
SGB10-500/10 |
1160 |
5230 |
1395 |
1340 |
1495 |
325 |
258 |
820 |
1070 |
1795 |
|||
SGB10-630/10 |
1345 |
6290 |
1450 |
1340 |
1550 |
325 |
268 |
820 |
1070 |
2265 |
|||
SGB10-630/10 |
1300 |
6400 |
1545 |
1340 |
1445 |
325 |
268 |
820 |
1070 |
1930 |
|||
SGB10-800/10 |
1520 |
7460 |
1590 |
1340 |
1490 |
330 |
273 |
820 |
1070 |
2450 |
|||
SGB10-1000/10 |
1770 |
8760 |
1680 |
1340 |
1555 |
330 |
276 |
820 |
1070 |
2640 |
|||
SGB10-1250/10 |
2090 |
10300 |
1710 |
1470 |
1635 |
335 |
286 |
820 |
1070 |
3170 |
|||
SGB10-1600/10 |
2450 |
12500 |
6 |
1800 |
1470 |
1770 |
350 |
330 |
1070 |
1070 |
3985 |
||
SGB10-2000/10 |
3050 |
15500 |
1850 |
1470 |
1890 |
350 |
346 |
1070 |
1070 |
4850 |
|||
SGB10-2500/10 |
3600 |
18400 |
1900 |
1470 |
2030 |
365 |
356 |
1070 |
1070 |
5620 |
Notes:The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.
We are pleased to deliver Transformer, Distribution Transformer, Power Transformer, Oil Transformer, Dry Type Transformer. Safe payment and on time deliver time will give you.If you want to know more about the product, please click here.
Send product request
Other supplier products
What Are the Common Drying Methods for Transformers? | The following are common drying methods for transformers such asH Class Dry Type Transformerfor your reference: (1) If the transformer drying ch... | |
Working principle of transformer | Three phase transformer Manufacturershares that transformer is a kind of electric appliance that transfers electric energy or transmits signal fr... | |
Amorphous alloy power transformer China | is a new type of energy saving transformer made of a new magnetic conducting material (amorphous alloy). It is more than 70% lower than the no-loa... | |
How to Dry the Transformer? | Transformers such asOil Immersed Transformerare sometimes wet, especially in the summer when the transformer is relatively powerful, and the power... | |
Why are some pebbles placed around the transformer? | Transformer is a kind of important equipment and type, such as thethree phase oil immersed transformer,which is constantly used in production and d... |
Same products
ACREL AID150 ALARM AND DISPLAY DEVICE | Seller: Jiangsu Acrel Electrical Manufacturing Co., LTD. | The AID150 insulation monitoring device schneideris designed for visual and audible indication of... | |
ACREL ANSVG STATIC VAR GENERATOR | Seller: Jiangsu Acrel Electrical Manufacturing Co., LTD. | ANSVG series of reactive power and harmonic hybrid compensation devices are connected in parallel... | |
The Working Principle of Active Power Filter | Seller: Jiangsu Acrel Electrical Manufacturing Co., LTD. | Active power filter is a new type of power electronic device used to dynamically suppress harmoni... | |
ACREL PZ72L-DE MULTIFUNCTION DC ENERGY METER | Seller: Jiangsu Acrel Electrical Manufacturing Co., LTD. | PZ series intelligent DC atorch electric energy meteris designed for applications such as DC pane... | |
ACREL DTSD1352-C SOLAR INVERTER SMART METER | Seller: Jiangsu Acrel Electrical Manufacturing Co., LTD. | Acrel sungrow smart meterDTSD1352 din rail type multi-function energy meter is an intelligent ins... |