Dry type Power Transformers
Product Description
SG (B) 10 series of non-encapsulated H-class dry-type power transformersadopt the special process technology of German (MORA) dry-type transformers to ensure that the products fully meet the requirements such as fire prevention, waterproof ,environmental protection. It is the ideal product for distribution systems and widely used in the subway, shipbuilding, mining, chemical, power companies and personnel-intensive buildings as well as other special requirements of the occasion for safety.
Model and Meaning
SC(B)10 Series Resin-insulated Dry Type Transformer
SG (B) 10 series Non-encapsulated H-class Dry-type Power Transformers
Technical Parameter for6kV, 10kV& 30kVA-2500kVA With Off Circuit Dry Type Transformer
|
Rated capacity(KVA) |
Voltage Combination |
Connection Group Symbol |
No-load Loss(W) |
Load Loss (W) |
No-load Current (%) |
Short-circuit Impedance(%) |
||||
|
High Voltage (KV) |
Tapping rangesof High Voltage |
Low Voltage(KV) |
130℃(B)(100℃) |
155℃(F)(120℃) |
180℃(H)(145℃) |
|||||
|
30 |
±2X2.5%±5% |
Dyn11Yyn0 |
190 |
670 |
710 |
760 |
||||
|
50 |
270 |
940 |
1000 |
1070 |
||||||
|
80 |
370 |
1290 |
1380 |
1480 |
||||||
|
100 |
400 |
1480 |
1570 |
1690 |
||||||
|
125 |
470 |
1740 |
1850 |
1980 |
||||||
|
160 |
540 |
2000 |
2130 |
2280 |
||||||
|
200 |
±2X2.5%±5% |
620 |
2370 |
2530 |
2710 |
|||||
|
250 |
720 |
2590 |
2760 |
2960 |
||||||
|
315 |
880 |
3270 |
3470 |
3730 |
||||||
|
400 |
980 |
3750 |
3990 |
4280 |
||||||
|
500 |
1150 |
4590 |
4880 |
5230 |
||||||
|
630 |
1340 |
5530 |
5880 |
6290 |
||||||
|
630 |
1300 |
5610 |
5960 |
6400 |
||||||
|
800 |
1520 |
6550 |
6960 |
7460 |
||||||
|
1000 |
1770 |
7650 |
8130 |
8760 |
||||||
|
1250 |
2090 |
9100 |
9690 |
10300 |
||||||
|
1600 |
2450 |
11000 |
11700 |
12500 |
||||||
|
2000 |
3050 |
13600 |
14400 |
15500 |
||||||
|
2500 |
3600 |
16100 |
17100 |
18400 |
||||||
|
1600 |
2450 |
1220 |
12900 |
13900 |
||||||
|
2000 |
3050 |
15000 |
15900 |
17100 |
||||||
|
2500 |
3600 |
17700 |
18800 |
20200 |
||||||
Notes:The load losses listed in the table are the values of the reference temperature for different insulation systems inparentheses; The load losses under other insulation system temperatures that are not included in the table should be according to their respective reference temperatures, the corresponding calculation is based on the"- 155 ℃(F)" insulation system temperature data.
Notes:The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.
Send product request
Other supplier products
| high voltage step up transformer | distribution transformer The products implement the National Standard GB1094-2013 Power Transformer and GB / T6451-2015 Three-phase Oil-immersed Po... | |
| How to see the oil position of oil-immersed transformer? | oil-immersed transformeroil level gage to 30 °, + 20 ° and + 40 °, respectively is refers to the oil-immersed transformer at ambi... | |
| Working principle of transformer | Three phase transformer Manufacturershares that transformer is a kind of electric appliance that transfers electric energy or transmits signal fr... | |
| How much damage does the electromagnetic radiation of the power transformer have on the body? | How much does the electromagnetism radiation of power transformer harm to the body? Distribution transformer substation suppliershares that with t... | |
| Cooling Method of Oil Immersed Power Transformer | In the operation of theOil Immersed Power Transformer, the heat of the winding and the iron core is first transmitted to the oil and then transmit... |
Same products
| China factory Transformer bushing BRDW-126/630-3 for power station | Seller: DONGFANG YOYIK (DEYANG) ENGNIEERING CO; LTD | "China factory Transformer bushing BRDW-126/630-3 for power station YOYIK is a research and devel... | |
| TOROIDAL TRANSFORMER | Seller: Yu Yang Magnetic Co., LTD | Seamless toroidal core (ferrite/powdered iron) minimizes core loss (<1.1W/kg) and achieves >... | |
| ACREL AID150 ALARM AND DISPLAY DEVICE | Seller: Jiangsu Acrel Electrical Manufacturing Co., LTD. | The AID150 insulation monitoring device schneideris designed for visual and audible indication of... | |
| ACREL ANSVG STATIC VAR GENERATOR | Seller: Jiangsu Acrel Electrical Manufacturing Co., LTD. | ANSVG series of reactive power and harmonic hybrid compensation devices are connected in parallel... | |
| The Working Principle of Active Power Filter | Seller: Jiangsu Acrel Electrical Manufacturing Co., LTD. | Active power filter is a new type of power electronic device used to dynamically suppress harmoni... |