Full-Scale Room Corner Fire Test Apparatus
Full-scale fire performance evaluation: Assess the fire behavior of wall and ceiling materials installed as in real applications.
Research and development: Study flame spread, smoke generation, and heat release of construction and decorative materials.
Fire safety certification: Evaluate materials for compliance with building codes and international fire safety standards.
Academic and scientific research: Investigate fire dynamics and corner fire phenomena that small-scale tests cannot replicate.
Compatible test components: Combustion chamber, smoke and sample gas collection system, gas analysis and data processing system, fuel supply system, sand-box burner.
Standards
This test apparatus conforms to a range of international and national standards:
GB/T 27904:2011 — Test method for flame spread of interior decoration materials
GB/T 25207:2010 — Classification of fire performance of building decorative materials
GB 8624:2012 — Classification of the burning behavior of building materials and products
ISO 9705:2016 — Full-scale room corner test for building materials
DS/ISO/TR 9705‑2 — Room corner fire test Part 2: Guidelines for material performance assessment
Parameters
| Parameter | Specification |
|---|---|
| Combustion Chamber Size | 2.4 m (L) × 3.6 m (H) × 2.4 m (W) |
| Smoke Hood Size | 3 m (W) × 3 m (D) × 1 m (H) |
| Weight | 700 kg |
| Sand-box Burner | Corner installation with 4–8 mm gravel and 2–3 mm sand, top surface flush with burner edge |
| Burner Ignition | Surface ignition (no electric spark) |
| Maximum Heat Output | 300 kW |
| Mass Flow Controller Range | 0–7 g/s, accuracy ≤1.5% |
| Smoke Sampling Flow | ≥13 L/min (diaphragm pump) |
| Optical Measurement Range | 400–750 nm, transmissivity accuracy 0.01% |
| Pressure Measurement | ±200 Pa, sensor response ≤1 s |
| Oxygen Analysis | Paramagnetic, 16–21% (V/V), response ≤12 s |
| Carbon Dioxide Analysis | IR type, 0–10% CO2. linearity ≤1%, response ≤12 s |
| Data Recording Interval | 3 s per record |
| Environmental Requirements | Power: 220V/10A, 380V/5KW; Temp: 10–35°C; Gas: propane, calibration gases: N2. CO2 |
Send product request
Other supplier products
| Medical needle toughness tester | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com The Medical Needle Toughness Tester is designed to evaluate the mechanical strengt... | |
| Bundesmann Water Repellency Tester - lab instrument | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com Email: serving@qinsun-lab。com TheTextile Bonded Door Drench Testeris a specialize... | |
| Fabric vertical flammability tester | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com Fabric vertical flammability testerApplications: VTEC Vertical Flammability Cha... | |
| Needle Flame Tester | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com Application The needle flame tester is widely used in various fields, including b... | |
| Cleanable Filter Media Test System | Application This system is used for: Cleanable Filter Media: Testing in accordance with VDI 3926-2. Filter Material Development: Optimization of... |
Same products
| Tabletop Xenon Arc Weathering Tester (SunMaster) | Seller: Standard Groups | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com The Water-Cooled Xenon Lamp Weat... | |
| Blow-By Test Rig | Seller: Standard Groups | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com Test system for the characterisa... | |
| Air filter System(ISO 16890/EN 779) | Seller: Standard Groups | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com Filter test system for general a... | |
| Oil Thread Leak Test System | Seller: Standard Groups | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com Test System for oil thread leak ... | |
| Manual HEPA/ULPA Filter Scanning Test System | Seller: Standard Groups | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com The Manual HEPA/ULPA Filter Scan... |