Building Material Fire Endurance Test Furnace OEM Manufacturer
Get a quote:
Whats/App: +86 156 1874 6768
Web: standard-groups.com
Features
The furnace incorporates advanced design and control technology to ensure stable, accurate, and repeatable testing.
Control System
Touchscreen and PC dual-control interface
Wireless connection supported; one PC can manage multiple furnaces
Automatic elimination of faulty thermocouples to maintain curve accuracy
Testing Performance
Full-automatic testing process from ignition to cooling
Real-time tracking of temperature and pressure curves
Automatic re-ignition if the flame is extinguished during testing
Automatic stop when reaching preset temperature or test duration
Safety and Reliability
Anti-power-off protection mode to avoid damage caused by sudden shutdown
Automatic cooling and exhaust system at the end of the test
Temperature deviation consistently lower than the limits required by GB standards
Data Management
Storage capacity for more than 100 sets of test data
Curve display for furnace temperature, back-surface temperature, and pressure
User-friendly interface for on-site operation or remote control
Parameters
| Item | Specification |
|---|---|
| Working Voltage | AC 220V ± 10%, 50 Hz |
| Power Consumption | 3 kW |
| Furnace Pressure Range | 0–100 Pa |
| Pressure Control Accuracy | 20 ± 3 Pa |
| Airflow Range | 0–50 m³/min |
| Airflow Accuracy | ≤ ±0.5 m³/min |
| Fuel Type | 0# or −10# diesel |
| Standard Fire-Curve Temperature Program | 60 min: RT–925°C; 120 min: RT–1050°C; 180 min: RT–1115°C; 240 min: RT–1150°C; 300 min: RT–1180°C; 360 min: RT–1210°C |
| Furnace Temperature Sensors | 4 pcs K-type armored thermocouples |
| Back-Surface Temperature Sensors | 2 pcs, accuracy ±4°C |
| Temperature Control Mode | Average or independent control |
| Heating Mode | Fully automatic diesel spray burner |
| Cooling Mode | Automatic exhaust and cooling |
| Timing Range | 0–360 min |
| Data Storage Capacity | ≥100 sets |
| Sample Size | 500 × 500 × 6 mm |
| Overall Dimensions | 1.6 m × 1.6 m × 1.6 m |
Test Procedures
1. Cut the sample using a 250mm × 90mm template. If the sample is a melt-shrinkable product, use a 250mm × 180mm template.
2. Clamp the sample in a 250mm × 90mm sample holder, tighten the wing nut, and secure the sample. The sample holder size for melt-shrinkable products is 250mm × 180mm. At this point, do not yet mount the sample holder onto the horizontal rod.
3. Turn on the power switch and set the ignition time to a slightly longer duration, such as 5 minutes. Select the appropriate positioning device according to the ignition method. After pressing "Start Test" and the burner stops at the 45° position, insert one end of the positioning device into the burner. Now mount the sample holder onto the horizontal rod and adjust the sample holder's up, down, left, and right positions to meet the test requirements. Remove the positioning device. Press the return key. After the burner resets, press "Test Reset".
4. Press and hold the ignition button, and simultaneously adjust the flame adjustment valve on the instrument panel. After igniting the gas, adjust the flame height to 20 ± 1mm. When adjusting the flame from large to small, it is easier to first tighten the flame adjustment knob on the panel. The height gauge should be at 20mm. Close the front door.
5. Place two pieces of filter paper in the collection tray and then place it under the sample.
6. Set the ignition time, press "Start Test," and the burner will automatically rotate to the 45° position and remain there for the set ignition time, then reset. The afterglow time starts counting simultaneously. If the sample stops afterglow before reaching the marked line, press "Stop Afterglow." If the sample afterglow reaches the marked line, immediately press "Stop Afterglow." Record the burning time.
7. Press "Test Reset" to stop the test. To continue the test, repeat the above steps; otherwise, turn off the power. Provided by Shandong Provincial Textile Science Research Institute.
Send product request
Other supplier products
| Rubber non-rotor vulcanization chamber | Whats/App: +86 156 1874 6768 Web: standard-groups.com Product Introduction: Non-rotor vulcanizer is a rubber processing industry control rubber ... | |
| ISO 25178 3D Optical Surface Profilometer Manufacturer China | Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com Large-Area 3D Optical Surface Profilometer is a high-performance three-dimens... | |
| AATCC Washer and Dryer | Get a quote: Whats/App: +86 156 1874 6768 Web: standard-groups.com The Washer-Dryer Combo integrates washing and drying functions into a single,... | |
| Suture Needle Penetration and Bending Strength Tester | Whats/App: +86 156 1874 6768 Web: standard-groups.com The Suture Needle Puncture and Bending Strength Tester has broad application prospects and ... | |
| Automatic Reaction Calorimeter | Whats/App: +86 156 1874 6768 Web: standard-groups.com This instrument is a professional testing instrument that simulates the specific process of... |
Same products
| Common Rail Injector Valve F00R J01 334 | Seller: 868983 | Common Rail Injector Valve F00R J01 334 Injector Valve Set F00V C01 361 Injector Valve Set F00V... | |
| Common Rail Injector Valve F 00V C01 371 | Seller: 868983 | Common Rail Injector Valve F 00V C01 371 Injector Valve Set F00V C01 310 Injector Valve Set F00... | |
| Common Rail Injector Valve F 00V C01 365 | Seller: 868983 | Common Rail Injector Valve F 00V C01 365 Injector Valve Set F00V C01 303 Injector Valve Set F... | |
| Common Rail Injector Valve F 00V C01 329 | Seller: 868983 | Common Rail Injector Valve F 00V C01 329 Injector Valve Set F00V C01 054 Injector Valve Set F... | |
| Common Rail Injector Valve F 00V C01 325 | Seller: 868983 | Common Rail Injector Valve F 00V C01 325 Injector Valve Set F00V C01 044 Injector Valve Set F... |