HYGK-303 Circuit Breaker Analyzer
Circuit breakeranalyzergeneralintroduction:
ThiscircuitbreakertesterisworkingonIEC62771,
thecircuitbreakeranalyzerhasanaccuratedisplayscreenandrotatinginterface.
Itistotestbouncetime,speed,contactingspace,travelandotherparameters.
Circuit breaker tester equipmenttestitems:
|
1 |
Closingandopeningtimemeasurementof12channels |
|
2 |
Maxdifferenceofclosingoropeningtimemeasurementofthreephases |
|
3 |
Bouncetimeandfrequencymeasurementofbreakerclosing |
|
4 |
Circuitbreakerclosingandopeningspeedmeasurement |
|
5 |
Travel-time,Coilcurrent-timecurveofcircuitbreakeroperationmeasurement |
|
6 |
Clearanceofcircuitbreakermeasurement |
|
7 |
VariableDCcircuitbreakeroperationpowersupply |
|
8 |
Printtestresultsbyinternalmicroprinters |
Circuit breakeranalyzer techniqueindex
|
1 |
Timemeasurementrange:6000ms,resolution0.1ms Timemeasurementerror:<1%RDG+0.2ms |
|
2 |
Speedmeasurement:Range2m/sresolution0.01m/smaxerror<0.1m/s Range20m/sresolution0.01m/smaxerror<0.2m/s |
|
3 |
Travelmeasurement:Range250.0mmresolution1mmmaxerror1mm |
|
4 |
DCPowerout:DC30V~250V/10A(instantaneous) |
|
5 |
9Travelsensorsconfiguration:gratingandangle |
|
6 |
Teststandard:IEC62271 |
|
7 |
LCD:128*64 |
|
8 |
Powersupply:AC220V±10%50Hz/60Hz |
|
9 |
Temperature:0~50°Chumidity:<85% |
|
10 |
Size:360mm*280mm*300mm |
|
11 |
Weight:7kg |
Send product request
Other supplier products
| HYPCIT Primary current injection tester | Introduction: HYPCIT series primary current injection tester is applied in power system for circuit breaker test, protection system test and curre... | |
| HY2305 Insulation Tester | Insulation Tester HY2305 RatedVoltage 250V 500V 1000V 2500V 5000V Measuring Range 0.0~99.9MΩ100~999MΩ1.00~10.0GΩ 0.0~99.9... | |
| Oil Type Hipot Tester | HIPOT Tester is applied in power system for insulation test of high voltage equipment. The typical application of the HIPOT tester is as follo... | |
| FRC series High Voltage Divider | Application FRC series high voltage divider is applied to measure AC/DC high voltage in metrology department of power system or high voltage test.... | |
| circuit breaker analyzer HYGK-307 | Circuit breaker analyzer introduction: 1) Measurement of closing time, opening time, time spread between poles, time spread between units of one p... |
Same products
| PHS‑25C Benchtop Digital pH Meter | Seller: Kelilong Electron Co.Ltd | Product Description: Equipped with BNC‑composite electrodes and power supplies adapt... | |
| PHS‑3C Automatic Calibration pH/Thermometer | Seller: Kelilong Electron Co.Ltd | Product Description: Equipped with BNC‑compatible combination electrodes and power s... | |
| KL‑016 Benchtop Digital pH Meter (Backlit Display) | Seller: Kelilong Electron Co.Ltd | Product Description: This instrument features a large‑screen digital display, extern... | |
| KL‑98 Professional Laboratory pH/ORP/Temperature Meter | Seller: Kelilong Electron Co.Ltd | Product Description: The PH‑98 Tester is an easy‑to‑operate, multi‑functional microp... | |
| KL‑03(I) Pen‑type High‑precision pH Meter | Seller: Kelilong Electron Co.Ltd | Product Description: This instrument is available in a variety of colors. Calibratio... |