On-line Combustible Gas Detector
Titan measuring range of 0-100%LEL on-line infrared combustible gas detector, widely used in petroleum, chemical, refining, gas transmission and distribution industries. The detector can monitor the gas concentration (%LEL), and output bus signal (two wire system, four wire system) or 4~ 20mA current signal, highlight LED display, three kinds of alarm, alarm point full range setting. When infrared remote controller is used for calibration, calibration can be set according to the concentration of calibration gas.
Shape Structure of On-line Combustible Gas Detector
The detector consists of a housing, a sensor suite and a display module. The shell is mainly composed of upper cover, glass, glass pressure ring, bottom box and dust cover. The shell plays the role of flameproof and protection. Display module components are mainly composed of circuit board and display mask. The sensor suite consists of a sensor module, a header body and a header mounting seat. The sensor module is directly connected with the detector housing through the anti-misinsertion standard digital interface.
Parameters of On-line Combustible Gas Detector
Test Gas |
Flammable gas (EX) |
|
Sensor Type |
Catalytic combustion type |
|
Sampling Methods |
Natural diffusion |
|
Detection Range |
0%LEL~100%LEL |
|
Working Voltage |
DC24V±25% |
|
Way to Work |
The continuous |
|
Working Temperature |
-40℃~70℃ |
|
Working Humidity |
≤95%RH (non-condensing) |
|
Work Pressure |
86kpa~106kpa |
|
Explosion-proof Way |
flameproof |
|
Explosion-proof Grade |
Ex d IIC T6 Gb |
|
The Basic Error |
Detection Range %LEL |
Error %LEL allowed |
0~100 |
±5 |
|
Setting Range of Alarm Points(Two-level alarm) |
The factory level alarm point can be set from 1%LEL to 25%LEL, the default value is 25%LEL; The factory level two alarm point is set at 50%LEL, which is adjustable. |
|
Alarm Way |
Audible and visual alarm (optional) |
|
Alarm Error |
≤±3%LEL |
|
Alarm Sound Level Strength |
> 75dB(1 m away from the buzzer) |
|
Alarm Light Visibility |
> 20m (in darkness) |
|
The Response Time |
< 30s |
|
Protection Grade |
IP54 |
|
Service Life of Sensor |
1 year or more |
|
Overall Dimensions |
184×156×92mm |
|
The Weight |
1600G (with alarm light) |
|
Maximum Operating Current |
110mA |
|
The Output Signal |
RS485/Power bus |
|
Baud Rate |
9600 |
|
Explosion-proof Joint Thread |
M20×1.5(mm) |
|
Applicable Cable Outer Diameter |
φ6~φ8(mm) |
|
Maximum Transmission Distance Between Detector And Host |
1Km |
Features of On-line Combustible Gas Detector
Titan measuring range of 0-100%LEL point type combustible gas detector.
Widely used in petroleum, chemical, refining, gas transmission and distribution industries. The detector can monitor the gas concentration (%lel), and output bus signal (two wire system, four wire system) or 4~ 20ma current signal, highlight led display, three kinds of alarm, alarm point full range setting. When infrared remote controller is used for calibration, calibration can be set according to the concentration of calibration gas.
If you want to know more about how does a cormbustible gas detector workand what is a combustible gas detector, please visit our website.
If you have needs to buy combustible gas detector, please leave us a message.
As a reliable explosion proof electronicsmanufacturer, we will provide more kinds of explosion proof electricalproducts for sale, anything you need, please contact us.
Отправить запрос, связаться с поставщиком
Другие товары поставщика
Intrinsically Safe Thermal Camera | Explosion-proof intrinsically safe thermal imaging camera, mode YRH650, explosion-proof mark Ex ib I Mb, can be used in dangerous environments such... | |
Explosion-proof PDA | Explosionproof PDAis a kind of handheld terminal equipment with operating system, CPU, battery, man-machine interface and other features, which can... | |
Explosion Proof Tablet | Intrinsically safe tablet pcadopts intrinsic-safe circuit design, suitable for inflammable and explosive harsh chemical environment, such as petrol... | |
Explosion Proof Tablet | Explosion proof tabletcomputer adopts intrinsic-safe circuit design, suitable for inflammable and explosive harsh chemical environment, such as pet... | |
Explosion Proof PDA | Explosion proof PDAis a kind of handheld terminal equipment with operating system, CPU, battery, man-machine interface and other features, and this... |
Похожие товары
ACREL ADL400 THREE-PHASE DIN RAIL ENERGY METER | Продавец: Jiangsu Acrel Micro-grid Research&Development Institute | AcrelADL400din-rail multifunctional energy meter is an intelligent instrument designed mainly for... | |
ACREL ADL3000-E 3-PHASE MULTI-FUNCTION AC ENERGY METER | Продавец: Jiangsu Acrel Micro-grid Research&Development Institute | ADL3000-Eadopts 35mm din rail installation structure. It is small in size, and can measure electr... | |
ACREL ADL200 SINGLE PHASE ELECTRIC METER WITH MODBUS | Продавец: Jiangsu Acrel Micro-grid Research&Development Institute | Single-phase electronic energy meter AcrelADL200is mainly used to measure single-phase active ene... | |
ACREL ACR10R-D16TE PV INVERTER METER WITH POWER MONITORING | Продавец: Jiangsu Acrel Micro-grid Research&Development Institute | ACR10R-D16TE PV inverter meter with power monitoring is suitable for energy-saving renovation pro... | |
ACREL ACR10R-DXXTEX BIDIRECTIONAL THREE-PHASE REFLUX MONITORING ENERGY METER | Продавец: Jiangsu Acrel Micro-grid Research&Development Institute | ACR10R-DxxTEx bidirectional three-phase re-flux monitoring energy meter is equipped with external... |