BMS for ESS
The energy storage battery management system consists of battery pack management unit (BMU module), battery cluster management unit (RCU module), system management unit (SCU module) and system display management unit (MM10 module). This lithium bms battery management systemsupports a maximum of 1500V energy storage system.
Topology of BMS ESSFeatures of BMS for ESS
3+1 level structure
Online program upgrade
Support bidirectional IO ports to achieve automatic address coding
Multi-ports environment supervision devices data access
Function of BMS for ESS
Battery information management
Cluster status monitoring
Cluster status analysis
Safety control and protection
Energy control management
Battery maintenance management
Communication port and protocol
Specification of BMSof Batteryfor ESS
BMU Module
Category |
Item |
Specification |
||||
Working environment |
Temperature |
Operating temperature:-20~+65°C |
Storage temperature:-40~+125°C |
|||
Working power |
Voltage/Power consumption |
Rated voltage:9~32Vdc(reverse connection protection) |
Rated power consumption: 120mW (without load) |
|||
Communication |
CAN |
Support 1-channel non-isolated CAN |
Communication rate: 250kbs |
|||
Collection |
Cell voltage collection |
Collection range: 0~5V |
Collection resolution: 1mV |
Collection accuracy: |
Collection rate:100ms |
Electrical isolation: |
+10≤t≤+45 °C, the accuracy ≤5mV; |
4149Vdc/2934Vac (8mm) |
|||||
-40~≤t≤125°C, the accuracy ≤8mV |
||||||
Cell temperature collection |
Collection range: -40~+125°C |
Collection resolution: |
Collection accuracy: |
Collection rate:200ms |
||
-20≤t≤+65°C, the accuracy≤1°C; |
||||||
-40≤t≤+125°C, the accuracy≤2°C |
||||||
Cell equalization |
Cell equalization control |
Support 24-channel cell passive equalization |
Equalization resistance: 33Ω |
Equalization temperature rise:≤45°C |
RCU Module
Category |
Item |
Specification |
|||||
Working environment |
Temperature |
Operating temperature:-20~+65°C |
Storage temperature:-40~+125°C |
||||
Communication |
CAN/RS485 |
Support 1 isolated CAN and 1 non-isolated CAN |
2 isolated RS485 |
||||
Collection |
Total voltage |
Collection range: 0~1500V |
Collection resolution: 0.1V |
Collection accuracy: |
Collection rate: |
Electrical isolation: |
|
collection |
Total voltage<1000V (≤±1%FS) |
100ms |
4149Vdc/2934Vac (8mm) |
||||
Total voltage ≥1000V (≤±0.5%FS) |
|||||||
Total current |
Collection range: ±1200A |
Collection resolution: 0.1A |
Module circuit collection accuracy: ±1200A, accuracy ±1%FS |
Collection rate: |
|||
collection |
200ms |
||||||
Insulation collection |
Collection range: 0~10MΩ |
Collection accuracy: accuracy≤3% (500V~1500V, ≥600KΩ) |
Collection rate: 60s |
||||
(adjust according to the Y capacitance value of the PCS device) |
|||||||
Temperature collection |
Collection range: -40~+125°C |
Collection resolution: 1°C |
Collection accuracy: |
Collection rate: |
|||
-20~+65°C, accuracy≤1°C; |
200ms |
||||||
-40~+125°C, accuracy≤2°C |
|||||||
Monitoring capability |
1 RCU module can max. manage 32 BMU modules |
SCU Module
Category |
Item |
Specification |
|
Working environment |
Temperature |
Operating temperature: |
Storage temperature: |
-20~+65°C |
-40~+125°C |
||
Communication |
LAN communication |
Communication rate: 10M/100M |
Electrical isolation: 3000Vdc |
CAN communication |
Communication rate: 250kbs |
Electrical isolation: 2500Vdc |
|
RS485 communication |
Communication rate: 9600kbs |
Electrical isolation: 2500Vdc |
|
RS232 communication |
Communication rate: 9600kbs |
Electrical isolation: 2500Vdc |
|
Storage |
Data record |
On-board eMMC |
External expansion TF |
storage space: 8G |
card storage space: 0~128G |
||
Insulation |
Communication |
LAN:3000Vdc |
CAN/RS485/RS232:2500Vdc |
Monitoring capability |
1 SCU module can max. manage 30 RCU modules |
MM10 Module
Category |
Item |
Specification |
|
Working environment |
Temperature |
Operating temperature: |
Storage temperature: |
-10~+60°C |
-20~+70°C |
||
Working power |
Voltage/Power consumption |
Rated voltage:9~30Vdc |
Rated power |
consumption:10W |
|||
Communication |
LAN |
1 isolated LAN |
Communication rate: |
10M/100M |
|||
Basic parameter |
micro USB port |
Support 1-channel micro USB for system |
|
programming and ADB debugging |
|||
Screen |
Capacitive touch screen |
||
Storage |
Data record |
eMMC storage space:8G |
TF card storage space: |
0~128G |
|||
Hardware parameter |
CPU processor |
RK3288/4 core frequency 1.6GHz |
|
Run system |
Android 7.1 |
||
GPU |
ARM Mail-T764 |
Отправить запрос, связаться с поставщиком
Другие товары поставщика
Battery Management System Used In Transport | Rail batteries are an important part of the rail transit power supply system. At this point, the monitoring and management of faults and states hel... | |
Wired Battery Monitoring System | Wired battery bank monitoring systemis a kind of smart battery monitoring system that provides real-time monitoring of normal battery parameters an... | |
H3G-THWL Battery Management System | H3G-TH WL wireless active balancing battery management systemadopts a new generation of ZigBee wireless communication technology, which reduces on-... | |
LM12.8V100Ah/200Ah LiFePO4 Deep Cycle Battery 12.8V 100Ah | This is used to provide sustained power output over long periods. The LiFePO4 batteries for sale are suitable for those applications which require ... | |
Portable Power | The portable rechargeable 24vdc power supplyis a clean energy product that integrates alternating current and direct current. This energy storage s... |
Похожие товары
Electric Motorcycle High Energy Lithium Battery | Продавец: Taizhou CGONEN New Energy Co., Ltd. | Our 60V26Ah/ 60V29Ah/ 60V32Ah NMC high-speed electric motorcycle high-energy lithium batteries re... | |
MECHANIC Max28 Battery Activation Board for iPhone 8-16 Pro Max & Android | Продавец: Phonefix | Mechanic Max28 battery activation detection board activates iPhone 6-16 Pro Max, VIVO OPPO Samsun... | |
PHONEFIX W23 Universal Battery Fixture For Spot Welding Machine | Продавец: Phonefix | PHONEFIX Professional Edition Battery Spot Welder Anti-static Welding Fixture for Mobile Phone Ba... | |
OSS T5 Lightning Type-C Micro Data Cable Detection Board | Продавец: Phonefix | OSS T5 Data Cable Detection Board quickly detect abnormal data cable issues, it can be connected ... | |
Portable Battery Power Station | Продавец: DongGuan Cham Battery Technology Co.,LTD | CHAM is a company that provides portable power stations, designed to offer a reliable power sourc... |