ACREL MEDICAL IT ISOLATED POWER SYSTEM
Acrel medical isolated power supplysystems are mainly used in operating rooms, ICU/CCU intensive care units, premature infant care units, delivery rooms, hemodialysis centres, and emergency rooms. The hospital isolated power systemsprovide safe, reliable and continuous power distribution for important equipment in these places. They can realize the conditions of insulation, load and isolation transformer temperature of IT system. Real-time monitoring with functions such as system insulation fault circuit location and centralized monitoring of multiple systems.
Medical Isolated Power Supply System For Sale
Hospital isolated power systems provide safety, continuous and reliable power supply, real-time detection of the insulation state to the ground to ensure the life safety of patients. Insulation fault location, convenient maintenance.
Hospital Isolated Power Systems Data Sheet
Technical Parameters of AITR Series of Medical Isolation Transformer |
|||||
Type |
AITR10000 |
AITR8000 |
AITR6300 |
AITR5000 |
AITR3150 |
Insulation class |
H |
H |
H |
H |
H |
Protection class |
IP00 |
IP00 |
IP00 |
IP00 |
IP00 |
Power/voltage/ current |
|||||
Rated power |
10000VA |
8000VA |
6300VA |
5000VA |
3150VA |
Rated frequency |
50/60Hz |
50/60Hz |
50/60Hz |
50/60Hz |
50/60Hz |
Rated input voltage |
AC230V |
AC230V |
AC230V |
AC230V |
AC230V |
Rated input current |
36A |
||||
Rated output voltage |
AC230V/115V |
AC230V/115V |
AC230V/115V |
AC230V/115V |
AC230V/115V |
Rated output current |
|||||
Inrush current |
<12In |
<12In |
<12In |
<12In |
<12In |
Leakage current |
<200μA |
<200μA |
<200μA |
<200μA |
<200μA |
No load input current |
|||||
No load output voltage |
235V±3% |
235V±3% |
235V±3% |
235V±3% |
235V±3% |
Short circuit voltage |
<6.9V |
<6.9V |
<6.9V |
<6.9V |
<7.5V |
General parameters |
|||||
Fuse wire |
80A |
63A |
50A |
35A |
25A |
Primary winding resistance |
<55mΩ |
<64mΩ |
<80mΩ |
<131 mΩ |
<245mΩ |
Secondary winding resistance |
<45mΩ |
<64mΩ |
<80mΩ |
<116 mΩ |
<228mΩ |
Iron loss |
<150W |
<105W |
<107W |
<77W |
<55W |
Copper loss |
<230W |
<200W |
<170W |
<125W |
<120W |
Efficiency |
>96% |
>96% |
>96% |
>96% |
>95% |
Maximum ambient temperature |
<40℃ |
<40℃ |
<40℃ |
<40℃ |
<40℃ |
No-load temperature rise |
<36℃ |
<33℃ |
<31℃ |
<26℃ |
<22℃ |
Full load temperature rise |
<65℃ |
<76℃ |
<67℃ |
<62℃ |
<55℃ |
Noise grade |
<40dB |
<40dB |
<40dB |
<40dB |
<40dB |
Isolated Power System Purpose
Medical isolated power panelsprovide safe, reliable and continuous power distribution for the important equipment at these locations:
Used for the transformation of TN system into IT system (ungrounded system)
Functions of real-time monitoring and fault alarming of the ground insulation resistance, transformer load current and transformer winding temperature of the monitored IT system
When the monitored IT system has an insulation fault, the medical isolation panel, hospital isolation panelcan initiate and generate the fault location signal to the system, and realize fault locating function with the help of the fault locator
Acrel isolation panel for operating roomscan remotely monitor the real-time operating conditions of up to 16 pieces of systems, and the main interface intuitively displays whether the access system communication is intact
Medica/Hospital Isolated Power Systems FAQs
What is hospital isolated power system?
It is an isolated power system operating roomthat conducts insulation monitoring and fault determination of the power distribution system, to further provide safe, reliable and continuous power distribution.
What are functions of medical isolated power panels?
What's the consists of medical isolated power supply system?
What are the applications of hospital isolated power systems?
If you want to know more kinds of split current transformer, please visit our website.
Send product request
Other supplier products
ACREL DJSF SERIES DC ENERGY METER | Acrel DJSF Series modbus dc power meterwith double channels DC input is mainly designed for telecom base station, DC charging pile, solar photovolt... | |
ENERGY MANAGEMENT DEVICES | As a specialized programmable energy metersupplier, Acrel provides various energy meter types for sale. Acrel Power Meters and Energy Management sy... | |
SMART GATEWAY | Acrel smart geteway currently include AWT100 wireless communication terminal, ANet smart gateway. these products mainly realizes the function of th... | |
ACREL ADW SERIES IOT POWER METER | Acrel ADW series energy meter using iotcompared with smart energy meter has the biggest advantage is that it can be controlled by wireless communic... | |
ELECTRICAL MONITORING & PROTECTION DEVICE | Acrel electrical overload protection devicesprovide solutions for 0.4kv-35kv power distribution system, which include programmable panel energy met... |
Same products
TL-3200 Desktop Digital Conference System | Seller: Gonsin Conference Equipment Co.,LTD. | TL-3200 digital conference system allows the delegate to speak, request to speak and listen to th... | |
Subwoofer Series | Seller: Gonsin Conference Equipment Co.,LTD. | Features of China SubwooferSeries GX-SP1018SSB-C / GX-SP1018DSB-C Polygonal guide hole design to... | |
Speaker Stand | Seller: Gonsin Conference Equipment Co.,LTD. | Technical Specifications of GX-B204 China Speaker Stand Installation Hanging ... | |
Simultaneous Interpretation System | Seller: Gonsin Conference Equipment Co.,LTD. | GONSIN Simultaneous Interpretation/Translation System & Equipment is suitable for business an... | |
Signal Splitter GX-ANT201-X | Seller: Gonsin Conference Equipment Co.,LTD. | Features of audio signal splitterGX-ANT201-X Ultra-high dynamic low noise components and ultra-w... |