ACREL MEDICAL IT ISOLATED POWER SYSTEM
Acrel medical isolated power supplysystems are mainly used in operating rooms, ICU/CCU intensive care units, premature infant care units, delivery rooms, hemodialysis centres, and emergency rooms. The hospital isolated power systemsprovide safe, reliable and continuous power distribution for important equipment in these places. They can realize the conditions of insulation, load and isolation transformer temperature of IT system. Real-time monitoring with functions such as system insulation fault circuit location and centralized monitoring of multiple systems.
Medical Isolated Power Supply System For Sale
Hospital isolated power systems provide safety, continuous and reliable power supply, real-time detection of the insulation state to the ground to ensure the life safety of patients. Insulation fault location, convenient maintenance.
Hospital Isolated Power Systems Data Sheet
Technical Parameters of AITR Series of Medical Isolation Transformer |
|||||
Type |
AITR10000 |
AITR8000 |
AITR6300 |
AITR5000 |
AITR3150 |
Insulation class |
H |
H |
H |
H |
H |
Protection class |
IP00 |
IP00 |
IP00 |
IP00 |
IP00 |
Power/voltage/ current |
|||||
Rated power |
10000VA |
8000VA |
6300VA |
5000VA |
3150VA |
Rated frequency |
50/60Hz |
50/60Hz |
50/60Hz |
50/60Hz |
50/60Hz |
Rated input voltage |
AC230V |
AC230V |
AC230V |
AC230V |
AC230V |
Rated input current |
36A |
||||
Rated output voltage |
AC230V/115V |
AC230V/115V |
AC230V/115V |
AC230V/115V |
AC230V/115V |
Rated output current |
|||||
Inrush current |
<12In |
<12In |
<12In |
<12In |
<12In |
Leakage current |
<200μA |
<200μA |
<200μA |
<200μA |
<200μA |
No load input current |
|||||
No load output voltage |
235V±3% |
235V±3% |
235V±3% |
235V±3% |
235V±3% |
Short circuit voltage |
<6.9V |
<6.9V |
<6.9V |
<6.9V |
<7.5V |
General parameters |
|||||
Fuse wire |
80A |
63A |
50A |
35A |
25A |
Primary winding resistance |
<55mΩ |
<64mΩ |
<80mΩ |
<131 mΩ |
<245mΩ |
Secondary winding resistance |
<45mΩ |
<64mΩ |
<80mΩ |
<116 mΩ |
<228mΩ |
Iron loss |
<150W |
<105W |
<107W |
<77W |
<55W |
Copper loss |
<230W |
<200W |
<170W |
<125W |
<120W |
Efficiency |
>96% |
>96% |
>96% |
>96% |
>95% |
Maximum ambient temperature |
<40℃ |
<40℃ |
<40℃ |
<40℃ |
<40℃ |
No-load temperature rise |
<36℃ |
<33℃ |
<31℃ |
<26℃ |
<22℃ |
Full load temperature rise |
<65℃ |
<76℃ |
<67℃ |
<62℃ |
<55℃ |
Noise grade |
<40dB |
<40dB |
<40dB |
<40dB |
<40dB |
Isolated Power System Purpose
Medical isolated power panelsprovide safe, reliable and continuous power distribution for the important equipment at these locations:
Used for the transformation of TN system into IT system (ungrounded system)
Functions of real-time monitoring and fault alarming of the ground insulation resistance, transformer load current and transformer winding temperature of the monitored IT system
When the monitored IT system has an insulation fault, the medical isolation panel, hospital isolation panelcan initiate and generate the fault location signal to the system, and realize fault locating function with the help of the fault locator
Acrel isolation panel for operating roomscan remotely monitor the real-time operating conditions of up to 16 pieces of systems, and the main interface intuitively displays whether the access system communication is intact
Medica/Hospital Isolated Power Systems FAQs
What is hospital isolated power system?
It is an isolated power system operating roomthat conducts insulation monitoring and fault determination of the power distribution system, to further provide safe, reliable and continuous power distribution.
What are functions of medical isolated power panels?
What's the consists of medical isolated power supply system?
What are the applications of hospital isolated power systems?
If you want to know more kinds of split current transformer, please visit our website.
在线联系供应商
Other supplier products
ISOLATED POWER SYSTEMS | Acrel Isolated power systems are mainly used in the medical and industrial sectors. The medical IT system is mainly designed for the large threat t... | |
SMART GATEWAY | Acrel smart geteway currently include AWT100 wireless communication terminal, ANet smart gateway. these products mainly realizes the function of th... | |
ACREL AMC SERIES DATA CENTER MONITOR MODULE | Acrel data center power distribution system solution is to improve the power efficiency of the data center and reduce the energy consumption of equ... | |
ISOLATED POWER SYSTEMS | Acrel wireless theft monitoring systemare mainly used in the medical and industrial sectors. The medical IT system is mainly designed for the large... | |
NEW ENERGY DEVICE | Acrel new energy insulation monitoring device abbis mainly used in solar PV system and EV charger. Nowadays, the world advocates a green, environme... |
Same products
CSD16301Q2 TRANSISTOR MOSFET N-CH 25V 6SON TEXAS INSTRUMENTS | 卖方: ZK Electronic Technology Co., Limited | Part Number:CSD16301Q2 Description:CSD16301Q2 TRANSISTOR MOSFET N-CH 25V 6SON TEXAS INSTRUMENTS ... | |
CAPACITOR EEF-CX0J10CAPACITOR EEF-CX0J101R PANASONIC SMD SPEC POLYMER 100UF 6.3V SMD LF1R PANASONIC SMD SPEC POLYMER 100UF 6.3V SMD LF | 卖方: ZK Electronic Technology Co., Limited | Part name:EEF-CX0J101R Description:CAPACITOR EEF-CX0J101R PANASONIC SMD SPEC POLYMER 100UF 6.3V ... | |
Heavy Copper PCB Manufacturer | 卖方: Xinfeng Huihe Circuits Co., Ltd. | Heavy Copper PCB, pcb fabrication up to 12oz, large current, pcb circuitfabrication base material... | |
8 Layer ENIG Half Hole Custom PCB | 卖方: Xinfeng Huihe Circuits Co., Ltd. | Number of layers: 8 Surface finish: ENIG Base material: FR4 Outer Layer W/S: 4/3mil Inner lay... | |
4 Layer ENIG Impedance Control Half Hole PCB Electric Circuit Board | 卖方: Xinfeng Huihe Circuits Co., Ltd. | Number of layers: 4 Surface finish: ENIG Base material: FR4 Outer Layer W/S: 6/4mil Inner lay... |