24KV SF6 Gas Load Break Switch
Application of 24KV SF6 Gas Load Breaker Switch
The SF6 gas-insulated switch is a three-phase interoperable switching device designed for use in distribution system cabling and overhead power line segment applications.
It can be operated manually in the field or remotely from the control center.
Technical parameters of 24KV SF6 Gas Load Breaker Switch
Products Type |
FWX-24 |
Basic Ratings |
|
Maximum System Voltage |
24kV |
Rated Continuous Current |
630A |
Rated Frequency |
50/60Hz |
Short Time Withstand Current |
16kA/1sec |
Making and Breaking Capacity |
|
Mainly Active Load Current |
630A |
Number of Load-break Operations |
400times |
Short-circuit Making Current (peak) |
40kA |
Number of Making Operations |
5 times |
Cable Charging Current |
25A |
Line Charging Current |
|
Closed Loop Circuit Current |
630A |
Transformer Magnetizing Current |
22A |
Power Frequency Withstand Current Test |
|
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters |
50kV |
DryCondition-1min,Ph- Ph, Phase to Earth |
64kV |
Dry Condition - 1 min Across Interrupter |
79kV |
Impulse Withstand Current Test( 1.2 x 50 µs ) |
|
Phase to Phase, Phase to Earth |
125kV |
Across Interrupter |
145kV |
Other Ratings & Specifications |
|
Internal Arc Test |
20kA /0.1 sec |
Arc Extinction Medium |
SF6 Gas |
Insulation Medium |
SF6 Gas |
Creepage Distance (Porcelain) |
700mm |
Creepage Distance (Silicon) |
1200mm |
Dry arcing distance |
≥ |
IP Level |
65 |
Operation Performance |
|
Closing/Opening Time |
<1sec |
Mechanical Operations (Guaranteed) |
10000times |
Operating Temperature (*Manual Type) |
-25~+70℃ |
Gas Pressure |
|
Nominal Pressure (MPa, at 20°C) |
|
Bursting Pressure (MPa) |
|
Minimum Gas Pressure (MPa) |
|
Leakage Rate (cc/ sec) |
≤0.5% |
Voltage sensors |
|
CT ABC 10P10 5VA |
400:05:00 |
Incoming side and outgoing side of the voltage sensor
6 Voltage sensor(built-in)
Phase voltage:(24(36)kV/√3)/(3.25V/√3)
Special attention should be paid to the voltage sensor, which must be directly fed by the switch.
No additional adjustment circuit can be added to the controller. The voltage signal of the switch into the test line needs to be tested separately.
Zhuhai GopowerSmart Grid Co., Ltd. is one of the earliest electric power equipment company. We provide 15kv load break switch, 15 kv pole mounted disconnect switch, lbs 24kv 630aand etc. Want to know more? Please contact us.
在线联系供应商
Other supplier products
24KV Vacuum Circuit Breaker | 24KV Vacuum Circuit Breaker The 24KV breaker switch unit is comprised of three poles, the operating mechanism, and the operating mechanism housing... | |
Centralized Type DTU | BD-163 distribution automation remote terminal (hereinafter referred to as the distribution terminal) is a new generation of power distribution ter... | |
33KV SF6 Gas Load Break Switch | Application of 33KV SF6 Gas Load Breaker Switch The switch is made of a proven rugged, corrosion-resistant material (304L stainless steel plate fo... | |
33KV SF6 Gas Load Break Switch | Application of 33kv auto recloser The 33kvpole mounted switchis made of a proven rugged, corrosion-resistant material (304L stainless steel plate ... | |
SF6 Gas 11KV Load Break Switch | The 11kv load break switchis suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and the rated frequency 5... |