33KV SF6 Gas Load Break Switch
Application of 33KV SF6 Gas Load Breaker Switch
The switch is made of a proven rugged, corrosion-resistant material (304L stainless steel plate for warships), ensuring a long service life (30 years) and a range of operations, with the characteristics ideal for on-column equipment.
Technical Parameters of 33KV SF6 Gas Load Breaker Switch
Products Type |
FWX-36 |
Basic Ratings |
|
Maximum System Voltage |
36kV |
Rated Continuous Current |
630A |
Rated Frequency |
50/60Hz |
Short Time Withstand Current |
16kA/1sec |
Making and Breaking Capacity |
|
Mainly Active Load Current |
630A |
Number of Load-break Operations |
400times |
Short-circuit Making Current (peak) |
40kA |
Number of Making Operations |
5 times |
Cable Charging Current |
25A |
Line Charging Current |
|
Closed Loop Circuit Current |
630A |
Transformer Magnetizing Current |
22A |
Power Frequency Withstand Current Test |
|
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters |
70kV |
DryCondition-1min,Ph- Ph, Phase to Earth |
95kV |
Dry Condition - 1 min Across Interrupter |
110kV |
Impulse Withstand Current Test( 1.2 x 50 µs ) |
|
Phase to Phase, Phase to Earth |
195kV |
Across Interrupter |
215kV |
Other Ratings & Specifications |
|
Internal Arc Test |
20kA /0.1 sec |
Arc Extinction Medium |
SF6 Gas |
Insulation Medium |
SF6 Gas |
Creepage Distance (Porcelain) |
1055mm |
Creepage Distance (Silicon) |
1550mm |
Dry arcing distance |
≥ |
IP Level |
65 |
Operation Performance |
|
Closing/Opening Time |
<1sec |
Mechanical Operations (Guaranteed) |
10000times |
Operating Temperature (*Manual Type) |
-25~+70℃ |
Gas Pressure |
|
Nominal Pressure (MPa, at 20°C) |
|
Bursting Pressure (MPa) |
|
Minimum Gas Pressure (MPa) |
|
Leakage Rate (cc/ sec) |
≤0.5% |
Voltage sensors |
|
CT ABC 10P10 5VA |
400:05:00 |
Incoming side and outgoing side of the voltage sensor
6 Voltage sensor(built-in)
Phase voltage:(24(36)kV/√3)/(3.25V/√3)
Special attention should be paid to the voltage sensor, which must be directly fed by the switch.
No additional adjustment circuit can be added to the controller. The voltage signal of the switch into the test line needs to be tested separately.
Zhuhai GopowerSmart Grid Co., Ltd. is one of the earliest electric power equipment ltd. We provide 33kv load break switch, load break switch 33kv, 11 kv breakerand etc. Want to know more? Please contact us.
在线联系供应商
Other supplier products
Control Box-Feeder Terminal Unit | The feeder terminal unit(FTU) is a new HV switch control device of control cabinet enclosures equipped with both the imported DSP high-speed sampli... | |
Control Box-Feeder Terminal Unit | The feeder terminal(FTU) is a new HV switch control device of control cabinet enclosuresequipped with both the imported DSP high-speed sampling chi... | |
15KV SF6 Gas Load Break Switch | 15KV SF6 Gas Load Break Switch 15 kv pole mounted disconnect switch is suitable for rated voltage 15kV, rated current 630A, 50/60Hz distribution n... | |
LBS 24KV 630a SF6 Gas Load Break Switch | LBS 24KV 630a SF6 Gas Load Break Switch 24kV SF6 load break switchis a sf6 load break switch for medium voltage switchgear, using SF6 gas as arc e... | |
Centralized Type DTU | The centralized DTU adopts high-performance MCU processor, high-speed industrial network communication technology, multi-CPU integration technology... |