SF6 Gas Load Break Switch 11kv

The 11 kv load break switch is suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and the rated frequency 50/60Hz, which can break off and close the load current and overload current in the power system. The 11 kv load break switchis equipped with an intelligent controller to realize the automation of the distribution system. Inquiry 11kv load break switch price.

SF6 Gas Load Break Switch 11kv Features

The operating mechanism with spring energy storage ensures fast closing and switching operation (<1000ms).

Operator place: Local/Remote.

11kv lbsequipped with an electronic controller, this pole mounted switch can be operated locally or with FTU/RTU interface for console operation.

SF6 Gas 11 kv Load Break Switch In Pole Mounted Switch Solution

The type of high-voltage bypass type SF6 insulated load switch is divided into manual type and electric type, which is an engineering bypass type load switch used for the maintenance and construction of distribution lines in order to make uninterrupted power supply to distribution lines. This load break switch 11kvuses SF6 gas which has outstanding insulation and arc extinguishing performance. Inquiry 11kv load break switch price. Check more pole mounted switch solutions.

Specification of SF6 Gas 11KV Load Break Switch PDF

Parameter Name

Unit

Technical Requirement

Rated Maximum Voltage

kV

12

Rated continuous Current

A

630

Short Time Withstand Current

kA

20

Short-circuit Making Current (peak)

kA

50

Power Operating Time (Close/Open)

sec

<2

Mechanical Operations

times

3000

Rated full load operations

times

400

Breaking Capacity

Main Active (0.7pf)

A

630

Cable charging

A

5

Transformer magnetizing

A

10

Lightning Impulse Withstand Level

Phase to Earth

kV

75

Across interrupter

kV

85

Power Frequency withstand voltage

Phase to Earth

kV

42

Across interrupter

kV

50

Other Ratings & Specifications

Creepage Distance (Silicon)

mm

830

IP Level

65

Arc Extinction Medium

SF6 Gas

Insulation Medium

SF6 Gas

Leakage Rate

cc/ sec

≤0.5%

Product size (max)

Width

mm/in

1368/54

Height

mm/in

530/21

Environmental Conditions for Equipment Use of SF6 Gas 11KV Load Break Switch

Environmental conditions for equipment use

height above sea level:≤3000m

Air temperature: -40℃~+50℃

Maximum diurnal temperature difference:≤25℃

Relative humidity:Daily mean95% monthly average90%

Maximum wind speed:≤34m/s

Earthquake intensity:<8 degree

Icing thickness: <10mm

Thickness of snow: <35mm

irradiance: <0.1W/cm2

Pollution grade: Ⅲ class, Ⅳ class Ⅲ, Ⅳ

Installation site: No fire disaster, explosion danger, chemical corrosion, and frequent strenuous vibration places

11 kv load break switch Working Procedure

The load switch that uses SF6 gas as insulation and arc extinguishing medium is called the SF6 gas load break switch. It can be used to switch and switch load current and overload current, and it can also be used to switch and switch no-load circuits, no-load transformers, and capacitors. Groups, etc., all three-position load switches with the functions of connecting, disconnecting, and grounding have the characteristics of simple structure and low price. But the load switch cannot disconnect the short-circuit current.

Intended Use of SF6 Gas 11KV Load Break Switch

The sf6 lbsswitch is an excellent load switch that many users have experienced in recent years. In addition to its long electrical life and strong braking force, it has the same advantages as the vacuum load switch. Its outstanding advantage is that it is easy to achieve three working positions (connected, disconnection and grounding), small current (inductance, capacitance) breaking, strong resistance to severe environmental conditions. It is suitable for popularization and application in urban and rural medium voltage distribution networks.

Gopoweris a professional electric power equipment company, we provide auto recloser, electrical control box, mcc electrical cabinets, mcc cabinets electricaland etc.



在线联系供应商

至: Dongguan Wanhang Electronics Technology Co., Ltd
Your E-mail:
消息正文:


Send to other suppliers

Other supplier products

15KV SF6 Gas Load Break Switch
15KV SF6 Gas Load Break Switch FWX1 LBS installed on the pole is suitable for rated voltage 12/24/40.5kV, rated current 630A, 50/60Hz Distribution network breaking. The load curr...
33KV SF6 Gas Load Break Switch
33KV SF6 Gas Load Break Switch Application of 33KV SF6 Gas Load Breaker Switch The 33kv load break switchis made of a proven rugged, corrosion-resistant material (304L stainless...
33KV SF6 Gas Load Break Switch
33KV SF6 Gas Load Break Switch These load break switch 33kvare intended for outdoor applications. They can be mounted either horizontally or vertically, and are suitable for elec...
11KV Auto Recloser Vacuum Circuit Breaker
11KV Auto Recloser Vacuum Circuit Breaker 11KV Auto Recloser Vacuum Circuit Breaker ZW32 series 11 kv outdoor vcbvacuum circuit breakers are used in distribution systems and pole mounted r...
Recloser Control Box-Feeder Terminal Unit
Recloser Control Box-Feeder Terminal Unit The feeder terminal unit(FTU) is a new HV switch control device of control cabinet enclosures equipped with both the imported DSP high-speed sampli...
供应产品

Same products

MONSA® DDAC-50
MONSA® DDAC-50 卖方: Guangzhou Monsa Chemical Co., Ltd INCI name: MONSA® DDAC-50 It functions by causing the cell membrane of bacteria to rupture...
MONSA® DCA-50
MONSA® DCA-50 卖方: Guangzhou Monsa Chemical Co., Ltd INCI name: disodium cocoampho diacetate Disodium cocoamphodiacetate for skinis a very mild amp...
MONSA® CTAC-50
MONSA® CTAC-50 卖方: Guangzhou Monsa Chemical Co., Ltd INCI name: Cetyl Trimethyl Ammonium Chloride Cetyl Trimethyl Ammonium Chloride is an ammonium ...
MONSA® CTAC-30
MONSA® CTAC-30 卖方: Guangzhou Monsa Chemical Co., Ltd INCI name: Cetyl Trimethyl Ammonium Chloride 30% Cetyltrimethyl ammonium chloride30% is mainly...
共轨喷油器
共轨喷油器 卖方: 德艾普(厦门)进出口有限公司 商品名称:柴油喷油器型号: 最小起订量:1 件 材质:钢 包装详情:纸箱包装 库存:有库存 品牌:CNDIP 质保:6个月