24KV Recloser Vacuum Circuit Breaker
The 24KV breaker switch unit is comprised of three poles, the operating mechanism, and the operating mechanism housing. The sequence of the poles is A -B – C or 1 – 2 - 3 (sequence left to right when viewed from the lower terminal side of the recloser switch unit.
Each 24kv vacuum circuit breakerby GOPOWER is embedded in a solid-insulated pole made of weather-proof cyclo aliphatic epoxy resin. This enables a small design as well as resistance against environmental effects.
Breaker principle and design of 24KV Vacuum Circuit Breaker
ZW32 series 24KV circuit recloser are used in distribution systems. 24kv vacuum circuit breakes are used to make and break normal and fault currents. Breakers are fully equipped with sensors and a controller to provide a means of protection and control. For more pole top switches at bulk price.
In case of a line fault, breakers can break and make currents several times, thus avoiding longer network interruptions due to temporary faults. The manufacture, design, and testing of the vacuum recloser is based on current standards IEC 62271-111:2019
Technical Parameters of 24KV Vacuum Circuit Breaker
Products Type |
ZW32-24 |
Maximum System Voltage |
24kV |
Rated Continuous Current |
630A |
Rated Frequency |
50/60Hz |
Short Time Withstand Current |
20kA/1sec |
Mainly Active Load Current |
630A |
Number of Load-break Operations |
30 |
Short-circuit Making Current (peak) |
50kA |
Number of Making Operations |
5 times |
Cable Charging Current |
25A |
Line Charging Current |
|
Closed Loop Circuit Current |
630A |
Transformer Magnetizing Current |
22A |
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters |
50kV |
DryCondition-1min,Ph- Ph, Phase to Earth |
65kV |
Dry Condition - 1 min AcrossInterrupter |
79kV |
Phase to Phase, Phase to Earth |
125kV |
Across Interrupter |
145kV |
Internal Arc Test |
20kA /0.1 sec |
Arc Extinction Medium |
vacuum |
Insulation Medium |
vacuum |
Creepage Distance (Silicon) |
960mm |
Dry arcing distance |
200mm≥ |
IP Level |
67 |
Closing/Opening Time |
<1sec |
Mechanical Operations (Guaranteed) |
10000times |
Operating Temperature (*Manual Type) |
-25~+70℃ |
As an electric power equipment ltd, we can offer sorts of related products for sale, if you are interested, please leave us a message.
在线联系供应商
Other supplier products
11KV Auto Recloser Vacuum Circuit Breaker | ZW32 series vcb 11kvoutdoor vacuum circuit breakers are used in distribution systems and pole mounted recloser. 11 kv outdoor vacuum circuit breake... | |
15KV SF6 Gas Load Break Switch | FWX1 LBS installed on the pole is suitable for rated voltage 12/24/40.5kV, rated current 630A, 50/60Hz Distribution network breaking. The load curr... | |
LBS 24KV 630a SF6 Gas Load Break Switch | 24kV SF6 load break switch is a sf6 load break switch for medium voltage switchgear, using SF6 gas as arc extinguishing and insulating medium. Rate... | |
Remote Terminal Unit-RTU | Remote terminal UNIT-RTU is a general term for various remote monitoring installed in the distribution network, which has functions such as data co... | |
SF6 Gas 11 KV Load Break Switch | The 11 kv load break switchis suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and the rated frequency ... |