Customizable Full-Scale Fire Test Room Apparatus
Whats/App: +86 156 1874 6768
Web: standard-groups.com
Standards
This test apparatus conforms to a range of international and national standards:
GB/T 27904:2011 — Test method for flame spread of interior decoration materials
GB/T 25207:2010 — Classification of fire performance of building decorative materials
GB 8624:2012 — Classification of the burning behavior of building materials and products
ISO 9705:2016 — Full-scale room corner test for building materials
DS/ISO/TR 9705‑2 — Room corner fire test Part 2: Guidelines for material performance assessment
Parameters
| Parameter | Specification |
|---|---|
| Combustion Chamber Size | 2.4 m (L) × 3.6 m (H) × 2.4 m (W) |
| Smoke Hood Size | 3 m (W) × 3 m (D) × 1 m (H) |
| Weight | 700 kg |
| Sand-box Burner | Corner installation with 4–8 mm gravel and 2–3 mm sand, top surface flush with burner edge |
| Burner Ignition | Surface ignition (no electric spark) |
| Maximum Heat Output | 300 kW |
| Mass Flow Controller Range | 0–7 g/s, accuracy ≤1.5% |
| Smoke Sampling Flow | ≥13 L/min (diaphragm pump) |
| Optical Measurement Range | 400–750 nm, transmissivity accuracy 0.01% |
| Pressure Measurement | ±200 Pa, sensor response ≤1 s |
| Oxygen Analysis | Paramagnetic, 16–21% (V/V), response ≤12 s |
| Carbon Dioxide Analysis | IR type, 0–10% CO2. linearity ≤1%, response ≤12 s |
| Data Recording Interval | 3 s per record |
| Environmental Requirements | Power: 220V/10A, 380V/5KW; Temp: 10–35°C; Gas: propane, calibration gases: N2. CO2 |
Features
Complete system: Includes combustion chamber, smoke and sample gas collection, gas analysis and data processing, and fuel supply systems.
Precision smoke collection: Conical hood with mixing devices ensures uniform smoke sampling and accurate gas analysis.
High-capacity exhaust: Stainless steel centrifugal fan, temperature-resistant to 300°C, adjustable flow rate ≥3.5 m/s.
Accurate mass and gas flow measurement: Mass flow controllers for propane and air ensure precise heat output.
Advanced optical and gas analysis: Measures O2. CO2. smoke density, and visible light transmissivity with high accuracy.
Realistic fire simulation: Sand-box burner mimics corner fire conditions with adjustable heat output from 100 kW to 300 kW.
Safety protection: UV flame monitoring and automatic shutdown prevent system hazards.
Integrated data acquisition: Records temperature, pressure, smoke density, and gas concentration in real time; includes software for calibration, analysis, and report generation.
Accessories
Combustion chamber with corner sand-box burner
Smoke collection hood and stainless steel ducting with mixing devices
Gas analysis system (O2 and CO2 analyzers)
Data acquisition and processing system with computer and printer
Mass flow controllers and calibration gases (N2. CO2)
Optical measurement system and thermocouples
Pressure sensors and smoke density measurement system
Test Procedures
Install materials in the combustion chamber according to their real-life application layout.
Connect propane fuel and calibration gases, and ensure all sensors and measurement devices are operational.
Ignite the sand-box burner and control gas flow to produce 100 kW heat output for the first 10 minutes.
If no flashover occurs, increase heat output to 300 kW and continue for another 10 minutes.
Monitor flame spread, heat release rate, smoke production, and oxygen/CO2 levels in real time.
Stop the test immediately upon observing flashover or after the 20-minute test period.
Analyze and export results using the integrated software.
Maintenance Information
Inspect and clean the combustion chamber, sand-box burner, and exhaust ducts regularly.
Calibrate O2 and CO2 analyzers, optical systems, and mass flow controllers periodically.
Check thermocouples, pressure sensors, and smoke sampling systems before each test.
Ensure exhaust fans and ducting are free of obstructions and capable of continuous operation.
Store propane and calibration gases according to safety regulations, and maintain ambient temperature within 10–35°C.
在线联系供应商
Other supplier products
| Surface Performance Tester STD-FB4 - A | Introduction TheSurface Tester analyzes finger movements-particularly, strokes-performed by artisans and professionals when judging a fabric&rsquo... | |
| Glove Cut Resistance Test meter | Product Introduction: The machine is used to test the cutting resistance of gloves. Under the specified load, the blade cuts the sample to measure... | |
| Luggage rod reciprocating fatigue testing machine | Luggage rod reciprocating testing machine for luggage rod reciprocating fatigue test. In the test, the specimen will be stretched to test the gap g... | |
| Dental Implants Static Torsion Testing Machine | Standard ISO 13498: Specifies static torsion testing protocols for dental implants, including torque application rates, failure criteria, and data... | |
| Socks wear tester | Whats/App: +86 156 1874 6768 Web: standard-groups.com Product Introduction: Socks wear tester is a special equipment, mainly used to test the we... |
Same products
| ISO 29463 HEPA/ULPA filter performance testing System | 卖方: Standard International Group (HK) Limited | Whats/App: +86 156 1874 6768 Web: standard-groups.com Standards The system supports and compli... | |
| High-Precision ISO 16890 Filter Media Test Rig for R&D and QC | 卖方: Standard International Group (HK) Limited | Whats/App: +86 156 1874 6768 Web: standard-groups.com Standards The system can execute and com... | |
| Mobile Floor Scrubber Aging Life Tester IEC 60312 | 卖方: Standard Groups | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com TheMobile Floor Scrubber Aging L... | |
| ISO 12103 Cleanable Filter Media Test System | 卖方: Standard International Group (HK) Limited | Whats/App: +86 156 1874 6768 Web: standard-groups.com Standards The system complies with: (1)... | |
| Robotic Vacuum Cleaners Edge-Following Tester | 卖方: Standard Groups | Get a quote: Whats/App: +86 185 0176 3615 Web: qinsun-lab.com TheEdge-Following Test Equipment... |
















