Circuit Integrity Under Fire Conditions Apparatus BS 6387
Standard
BS 6387
Feature
Control cabinet parameters:
1.With double flow meters and pressure regulators.
2.Automatic control of the testing process
3.Intelligent detection function, when a short circuit in the sample during the test, automatic alarm and turn off the heat source
4.Display: touch screen display temperature curve
5.Timer: 0 to 9 hours 99 minutes 99 seconds
6.Size of control cabinet: 650 (L)mm X400 (W)mm X1200 (H)mm
7.Load: 0 ~ 600V test voltage is adjustable;
8.Load current range: 0.1 ~ 3A, test current can be adjusted standards, but more than 3A is protected;
9.Load capacity should be able to ensure the test current approaches 3A can still ensure the test to continue testing. Also apply to spray test and hammering test load requirement
Fire Resistance:
1.Thetube-type gas burner with a burner facelength of 610 mm, which produces a line of closely spaced flames using propane with a forced air supply.
2.Installation and testing of the cable ladder fastened to the supporting steel chassis; the testing process can be adjusted on both sides of the vertical component testing ladder depending on cable size requirements (test stand length: 1200mm, height: 60mm, total weight: 18 ± 1kg)
3.Metal ring inside diameter is about: 150 mm.
4.With a temperature measuring device (diameter less than 2mm K-type thermocouple, from the flame ports 75mm).
5.The front end of the burner shall be no less than 200mm from the bottom and no less than 500mm from the wall.
6.According to the test grade, the flame temperature is adjustable: 600 ~ 1000℃
7.The horizontal distance between the center of the burner test cable 40-60MM, the vertical axis from the longitudinal axis of the specimen cable burner 100-120MM
8.Provide standards of five inner diameter of about 150 mm from metal rings, metal ring distance can be freely adjusted to facilitate sample fixed hold.
9.Stainless steel sample tray, load 30kg
Mechanical shock:
1. Stainless steel bracket impact structure;
2. Shock bar 25 mm in diameter and 600 mm long.
3. Once every 30S the bar drops under its own weight from an angle of 60° to the horizontal to strike the top of the wall at its midpoint .
4. Motor driven the shock bar periodicity.
5. Strike cycle (time): 10~999S(can be set freely,standard require 30 ± 2S / time;)
6. Total test time: 0 ~ 9999S
7. The ribbon-type propane gas burner with a nominal burner face length of 500 mm with a Venturi mixer (a centre-feed burner is recommended) and a nominal burner face width of 10 mm with three staggered rows of drilled holes, nominally 1.32 mm in diameter and drilled at 3.2 mm centres. (Shared with Fire Resistance part)
8. Test temperature of 600 ~ 1000 ℃ can be set freely.
9. Thermocouple diameter is less than ¢ 2mm. (Shared with Fire Resistance part)
10. Each phase of cable through 0.25A of current test.
Water spray:
1.The ribbon-type propane gas burner with a nominal burner face length of 500 mm with a Venturi mixer (a centre-feed burner is recommended) and a nominal burner face width of 10 mm with three staggered rows of drilled holes, nominally 1.32 mm in diameter and drilled at 3.2 mm centres..
2.Test temperature of 600 ~ 1000℃ can be set freely.(standard require 650 ±40 ℃).
3.With a diameter of not more than ¢ 2 of the thermocouple.
4.Supplying water at an approximately constant supply pressure sufficient 250 ~ 350Kpa to give a rate of water application in the vicinity of the cable sample between 0.25 L/m2/s and 0.30 L/m2/s.
5.The sample to be tested shall be a piece of the completed cable at least 1500 mm long, with approximately 100 mm of the sheath and outer covering removed from each end.
6.Test cable when powered by an isolation transformer, and is connected to the 3A fuse or circuit breaker, as well as each phase of the cable off lights indication.
Specification
Model STD-BS6387T
Test Bench2500(L)×800(W)×1.600(H)mm
Control Cabinet650 (L) X400 (W) X1200 (H)mm
Water Spray1500 (L) X1100 (W) X1400 (H)mm
Weight200kg
ManualProvided
在线联系供应商
Other supplier products
| Catheter Flexibility Tester | Main Uses The catheter flexibility tester is mainly used to evaluate the flexibility and durability of catheters or guidewires during bending or t... | |
| Safety hat electrical insulation performance tester | Product Introduction: Safety hat electrical insulation performance tester used to test the electrical insulation performance of safety hat, high d... | |
| VOC Emission Test Chamber for Flooring | Standard ISO 16000-9(Indoor Air - Determination of Volatile Organic Compounds) ASTM D5116(Standard Guide for Small-Scale Environmental Chamber ... | |
| Wet leakage current test system of photovoltaic device | Standard IEC 61215: Terrestrial Photovoltaic (PV) Modules – Design Qualification and Type Approval UL 61730: Safety Standard for Photovolta... | |
| Initial Adhesion Tester | The initial - tack tester, also known as the initial - tack property tester or adhesive tape tackiness tester, is an instrument specifically used t... |
Same products
| Adjustable flame length tester | 卖方: Standard International Group (HK) Limited | Whats/App: +86 156 1874 6768 Web: standard-groups.com Standard GB/T 5169.5: Electrical & E... | |
| Fabric Flame Retardant Tester | 卖方: 上海千实精密仪器 | Product details A method is used to determine the damaged area and the length of the damage when... | |
| Burning Manikin System | 卖方: 上海千实精密仪器 | Product details The burning manikin system is used to test the overall thermal protection perfor... | |
| Steel Structure Fireproof Coatings | 卖方: 上海千实精密仪器 | Product Introduction: Heat insulation efficiency and fire resistance test furnace of steel struc... | |
| Building material combustion calorific value calorimeter | 卖方: 上海千实精密仪器 | Product details Building material combustion calorific value calorimeter Mainly used for the det... |