11KV Auto Recloser Vacuum Circuit Breaker
ZW32 series 11 kv outdoor vacuum circuit breakers are used in distribution systems and pole mounted recloser. 11kv outdoor circuit breakers are used to make and break normal and fault currents. 11kv outdoor vcbs are fully equipped with sensors and a controller to provide a means of protection and control. In case of a line fault, breakers can break and make currents several times, thus avoiding longer network interruptions due to temporary faults.
The manufacture, design, and testing of the 11 kv outdoor vacuum circuit breakers by our electric power equipment ltdChina is based on current standards IEC 62271-100. We can give you the most competitive 11kv circuit breaker price.
11 KV Outdoor Vacuum Circuit Breaker Application
The 11 kv breakeris equipped with one integrated current transformer per pole. The current transformer has a ratio of 600 A:5A.
VCB rating for 11kvRecloser is for protection purposes and optimized for operation with the controller. For more pole top switches at bulk price.
VCB 11KVAuto Recloser Technical Parameters
Products Type |
ZW32-12 |
Maximum System Voltage |
12kV |
Rated Continuous Current |
630A |
Rated Frequency |
50/60Hz |
Short Time Withstand Current |
20kA/1sec |
Mainly Active Load Current |
630A |
Number of Load-break Operations |
30 |
Short-circuit Making Current (peak) |
50kA |
Number of Making Operations |
5 times |
Cable Charging Current |
25A |
Line Charging Current |
|
Closed Loop Circuit Current |
630A |
Transformer Magnetizing Current |
22A |
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters |
45kV |
DryCondition-1min,Ph- Ph, Phase to Earth |
42kV |
Dry Condition - 1 min AcrossInterrupter |
48kV |
Phase to Phase, Phase to Earth |
75kV |
Across Interrupter |
85kV |
Internal Arc Test |
20kA /0.1 sec |
Arc Extinction Medium |
vacuum |
Insulation Medium |
vacuum |
Creepage Distance (Silicon) |
780mm |
Dry arcing distance |
≥200mm |
IP Level |
67 |
Closing/Opening Time |
<1sec |
Mechanical Operations (Guaranteed) |
10000times |
Operating Temperature (*Manual Type) |
-25~+70℃ |
Отправить запрос, связаться с поставщиком
Другие товары поставщика
11KV Auto Recloser Vacuum Circuit Breaker | ZW32 series 11 kv outdoor vacuum circuit breakers are used in distribution systems and pole mounted recloser. 11 kv outdoor vacuum circuit breakers... | |
Products | Electric Power Equipment & Supplies Electrical Power Equipment & Supplies: Directly related to the production of electrical energy and tran... | |
15KV SF6 Gas Load Break Switch | 15 kv pole mounted disconnect switch is suitable for rated voltage 15kV, rated current 630A, 50/60Hz distribution network breaking. The load curren... | |
11KV Vacuum Circuit Breaker | ZW32 series Breakers are used in distribution systems. Circuit breakers are used to make and break normal and fault currents. Breakers are fully eq... | |
Pole Mounted Switch | The pole mounted disconnect switchis a kind of safety switch used on the electric pole to ensure the safety of electricity. Its main function is to... |