11KV Auto Recloser Vacuum Circuit Breaker
ZW32 series 11 kv outdoor vacuum circuit breakers are used in distribution systems and pole mounted recloser. 11kv outdoor circuit breakers are used to make and break normal and fault currents. 11kv outdoor vcbs are fully equipped with sensors and a controller to provide a means of protection and control. In case of a line fault, breakers can break and make currents several times, thus avoiding longer network interruptions due to temporary faults.
The manufacture, design, and testing of the 11 kv outdoor vacuum circuit breakers by our electric power equipment ltdChina is based on current standards IEC 62271-100. We can give you the most competitive 11kv circuit breaker price.
11 KV Outdoor Vacuum Circuit Breaker Application
The 11 kv breakeris equipped with one integrated current transformer per pole. The current transformer has a ratio of 600 A:5A.
VCB rating for 11kvRecloser is for protection purposes and optimized for operation with the controller. For more pole top switches at bulk price.
VCB 11KVAuto Recloser Technical Parameters
Products Type |
ZW32-12 |
Maximum System Voltage |
12kV |
Rated Continuous Current |
630A |
Rated Frequency |
50/60Hz |
Short Time Withstand Current |
20kA/1sec |
Mainly Active Load Current |
630A |
Number of Load-break Operations |
30 |
Short-circuit Making Current (peak) |
50kA |
Number of Making Operations |
5 times |
Cable Charging Current |
25A |
Line Charging Current |
|
Closed Loop Circuit Current |
630A |
Transformer Magnetizing Current |
22A |
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters |
45kV |
DryCondition-1min,Ph- Ph, Phase to Earth |
42kV |
Dry Condition - 1 min AcrossInterrupter |
48kV |
Phase to Phase, Phase to Earth |
75kV |
Across Interrupter |
85kV |
Internal Arc Test |
20kA /0.1 sec |
Arc Extinction Medium |
vacuum |
Insulation Medium |
vacuum |
Creepage Distance (Silicon) |
780mm |
Dry arcing distance |
≥200mm |
IP Level |
67 |
Closing/Opening Time |
<1sec |
Mechanical Operations (Guaranteed) |
10000times |
Operating Temperature (*Manual Type) |
-25~+70℃ |
Send product request
Other supplier products
VCB Pole Mounted Recloser | ZW32 series vacuum circuit recloser, produced by Gopower pole mounted auto recloser manufacturer, is used in distribution systems. Pole mounted aut... | |
SCADA Remote Terminal Unit RTU | As one of the top SCADA RTU manufacturers,Remote terminal unit scada is a general term for various remote monitoring installed in the distribution ... | |
33KV SF6 Gas Load Break Switch | These load break switch 33kvare intended for outdoor applications. They can be mounted either horizontally or vertically, and are suitable for elec... | |
Pole Top Switches | The pole mounted disconnect switch is a kind of safety switch used on the electric pole to ensure the safety of electricity. Pole top switch's main... | |
LBS 24KV 630a SF6 Gas Load Break Switch | LBS 24KV 630a SF6 Gas Load Break Switch 24kV SF6 load break switch is a sf6 load break switch for medium voltage switchgear, using SF6 gas as ar... |