ACREL DJSF SERIES DC ENERGY METER
Acrel DJSF Series modbus dc power meterwith double channels DC input is mainly designed for telecom base station, DC charging pile, solar photovoltaic and other applications. This series of meters can measure voltage, current, power and positive and negative energy in the DC system.
DJSF Series DC Energy Meter For Sale
● RS485 communication, Modbus-RTU protocol ● kWh, kVarh, Power, Current, Voltage measure ● suitable for Charging Pile; Solar PV, battery system ● two channel dc circuits, event recording, max demand
DJSF1352-RN Din Rail kWh Meter DC
DJSF Series DC Energy Meter Datasheet
Technical parameters |
Indicators |
||
Input |
Nominal value |
Voltage input range |
Current input |
DC 0-1000V |
Shunt:0-75mV; |
||
See the physical wiring diagram |
Hall sensor:0-20mA、4-20mA、0-5V,0-10V and so on. |
||
Overload |
|||
Power consumption |
Voltage: ≤0.2VA, current ≤0.1VA |
||
Accuracy class |
Class 1 |
||
Function |
Display |
8-bit segment LCD screen (LCD) |
|
Communication Interface |
RS485, infrared |
||
Communication protocol |
Modbus-RTU, DL/T 645-2007 |
||
Switch |
Switch output |
2 Relay outputs, 2A/30VDC or 2A/250VA |
|
Switch input |
2 dry contact inputs |
||
Pulse output |
A second pulse output, a energy pulse output |
||
See the SYS->PLUS display in the meter menu setting |
|||
For example: The meter displays 100, which is 100imp/kWH |
|||
Power Supply |
Voltage range |
AC/DC 85-265V or DC24V(±10%) or DC48V(±10%) |
|
Power consumption |
≤ 3W |
||
Power frequency withstand voltage |
Power supply // Voltage input // Current input // Relay output and switch input // Communication interface / / Pulse output 3kV/1minPower supply // Relay output // Voltage input // Current input 3kV/1minPulse output // Communication interface // Switch input 2kV/1min |
||
Insulation resistance |
≥ 40M Ω |
||
Average barrier-free working hours |
≥50000h |
||
Environment |
Temperature |
Normal operating temperature: -25 °C ~ +65 °C; |
|
Limit working temperature: -40 °C ~ +70 °C; |
|||
Storage temperature: -40℃~+80℃ |
|||
Humidity |
≤93%RH, no condensation, no corrosive gas |
||
Altitude |
≤2500m |
How Does A DJSF Series DC Energy Meter Work?
DJSF1352-RN has two channels dc circuits input. The input voltage shall not be higher than 120% of the rated input voltage of the product. 1A fuse shall be installed at the voltage input end. The current input should be external shunt or Hall current sensor. The instrument provides RS485 communication interface and supports Modbus-RTU protocol. Theoretically, up to 128 instruments can be connected on a line at the same time. Each instrument can set its Addr and baud, and also can be selected by setting.
DJSF Series DC Energy Meter FAQs
what is a DJSF DC energy meter?
DJSF dc energy meter with rs485is designed for DC screen, solar power supply, telecom base station, subway and other applications.
how does a DJSF DC energy meter work?
The DC voltage and the DC current are measured separately with two DMM, and the results are multiplied to get the DC power.
How does a DJSF energy meter Installation?
use 35mm guide rail which is convenient and quick to install.
Which signal input does DJSF dc energy meter support?
voltage supports 1000V input, current supports shunt (0-75mV), Hall sensor (0-20mA, 4-20mA, 0-5V) access.
Now the price of power meter for solar panelsis low, if you are interested, please contact us.
Отправить запрос, связаться с поставщиком
Другие товары поставщика
ENERGY MANAGEMENT DEVICES | As a specialized programmable energy metersupplier, Acrel provides various energy meter types for sale. Acrel Power Meters and Energy Management sy... | |
NEW ENERGY DEVICE | Acrel new energy insulation monitoring device abbis mainly used in solar PV system and EV charger. Nowadays, the world advocates a green, environme... | |
ISOLATED POWER SYSTEMS | Acrel wireless theft monitoring systemare mainly used in the medical and industrial sectors. The medical IT system is mainly designed for the large... | |
SMART GATEWAY | Acrel smart geteway currently include AWT100 wireless communication terminal, ANet smart gateway. these products mainly realizes the function of th... | |
ACREL DTSD1352-C SOLAR INVERTER SMART METER | Acrel sungrow smart meterDTSD1352 din rail type multi-function energy meter is an intelligent instrument designed mainly for energy statistics and ... |