2021 New design automatic circuit recloser/ Auto recloser
TD-CHZ16 protector integrates intelligent control functions such as over-current and short-circuit protection, under-voltage/over-voltage protection, leakage protection, remote communication management/fault memory, detection before closing, and automatic reclosing device. The new generation TD-CHZ16 protector has the characteristics of intelligence, safety, wide application range, stability and long service life.
Auto Recloser Function
When the current of the auto-reclosing leakage protector is greater than 3 times the rated current, the auto-reclosing leakage protector will be disconnected within 0.1 second to ensure the safety of the equipment.
The leakage current of TD-CHZ16 factory setting is 30ma. When a 15~30mA leakage occurs on the wire, the automatic reclosing will be disconnected within 0.1 second.
TD-CHZ16 type protector realizes the rated current 6A-10A-16A adjustable, and the maximum support is 16A. When the current is greater than 1.15 times the rated current, the auto-reclosing will monitor the duration and magnitude of this current; if the duration exceeds 3 seconds or is greater than 3 times the rated current, The automatic reclosing leakage protection switch is disconnected for protection
When the supply voltage is higher than 275V±5V, the auto-reclosing will be disconnected. After the voltage drops back to normal, the auto-reclosing will automatically close and energize.
When the power supply voltage is lower than 150V±5V, the automatic reclosing will be disconnected. After the voltage rises to normal, the automatic reclosing will automatically close, The power-on operation status is normal.
The automatic reclosing detects the line voltage before closing. When the power supply voltage is abnormal under-voltage or over-voltage, it will block the closing
and Alarm; if the fault is not eliminated, the switch cannot be closed and energized. When the fault is removed, the switch will automatically close and energize.
When there is an instantaneous leakage or an instantaneous impact on the line, such as lightning, socket flashover, etc., and there may be danger, the automatic reclosing leakage protector will be disconnected immediately;
After the fault, if the line is safe, the auto-reclosing will automatically reclose and energize. The number of closing times is unlimited
Technical Parameter of Adjusted Automatic Circuit Recloser
Model |
TD-CHZ |
Feature The working current is 16A, the leakage current can be adjusted, built-in lightning protection module, the discharge current can reach 10KA |
|
Working voltage Un |
220V 50HZ |
385V |
|
Rated load current RLA |
16A(6A/10A/16A) |
Overcurrent action current |
|
The inert current of leakage |
15 mA |
Leakage action current (adjustable) |
30 mA |
Overvoltage operating voltage (factory adjustable) |
275V±5V |
Undervoltage operating voltage (factory adjustable) |
150V±5V |
Overcurrent disconnect action time |
≤2s |
Short circuit disconnection operation time |
≤0.1 s |
Leakage disconnect action time |
≤0.1 s |
Overvoltage, undervoltage |
≤0.5s |
Disconnect time |
|
Load impedance that allows reset |
10 Ω |
Lightning resistance |
10KA () |
Voltage detection before closing |
Yes |
Reclosing time(factory adjustable) |
60s/120s/300s/1800s/3600s-10 次 |
Specification and installation |
95mm*93mm*65mm, DIN-rail |
If you want to know more details of auto recloser working principle, please visit our website.
Techwin Inc. is one of the most professional surge protector manufacturers in China. With matured experience in surge protection technology, Techwin surge protection devices manufacturer, whose spd surge arresters obtained 28 technology patents and multiple certifications such as CE, ROHS, TUV, UL, CQC, ISO9001, ISO14001, ISO45001 and so on. Telecom, electric power, CCTV, railway, intelligent transportation, solar wind power, petrochemical engineering and other industries all need spd protection devices, our lightning surge protectorfactory can provide surge protector arresters in line with the latest international and domestic standards.
Send product request
Other supplier products
SPD for Power Supply | Power surge protector, also known as the lightning protector, is suitable for AC 50/60HZ, rated voltage 220V/380V power supply system, to protect i... | |
100KA DIN-rail Mounted Large Discharge Current AC Power SPD | M100 series power supply system AC modules are mainly applicable to the power distribution systems for class I / type 1 protection. Type 1 spd surg... | |
Smart Groud Resistance Meter | Telecom, electric power, CCTV, railway, intelligent transportation, solar wind power, petrochemical engineering and other industries all need spd p... | |
Large Discharge Currrent TVSS Lightning Protection Box | The lightning power/circuit tvss breaker box is a kind of lightning surge protection device (SPD), which is mainly installed in the power distribut... | |
DIN-rail mounted DC power Surge protective device(SPD) | DC power supply SPD, also called DC lightning arrestor or DC surge suppressor, is designed for the protection of DC power circuit from the damage o... |