Cone Calorimeter Heat Release Test Machine

Whats/App: +86 156 1874 6768

Web: standard-groups.com

Products

Heat release quantity is the core parametersto evalatethe fire behavior of materials and products.TESTech'sCone Calorimeter canmeet all existing standards (including ISO 5660. ASTM E 1354. ASTM E 1474. ASTM E 1740. ASTM F 1550. ASTM D 6113.NFPA 264.CAN ULC 135 and BS 476 Part 15).This equipment includes these systems such as heat release, mass loss, smoke generation,etc,and allow users to buy the parts they need one by one and add into the same chamber.This flexible feature is one of it'sadvantages.

Cone Calorimeter test theory is based onthe principle that the burn calories is proportional to the amount of oxygen's consumption,1KGoxygen consumption will produce 13.1 MJ heat.Test gas heat emission, ignition timing, oxygen consumption rate, CO/CO2generation rate, the gas flow will be measured all. Cone Calorimeter DAQ system can help users to easily control the entire test. 19 "touch screen can help realizing the automatictesting and reducing installation space. In addition, users can alsochangethe sample temperature, or adjust the temperature rise time to test,after settingup the virtual temperature at real fire conditions. This method can obtain thesimilar test resultsto real fire environment.

Standards

• ISO 5660: Reaction to fire tests - the rate of heat release, smoke generation rate and mass loss rate.

• ASTM E 1354: Standard Test Method of materials heat and visible smoke release rate.

• BS 476 Pt.15: Building materials and structures test: - Test method for heat release rate of products.

• NFPA 264

Structural features

19-inch standard cabinetof integrated design, elegant, and easy to operate.

Conical Heater of 230V, 5000W, the heat output of 0 ~ 120 kW / m2.

19-inch touch-screen computer controlling the entire testing process.

Automatic ignition system,and automatic burning time calculation.

3 pieces K-thermocouples and 3 PID temperature controllers for temperature regulation.

Split gate -To protect samples area before the test, and insure the initial measurement stability.The operator could have extra time to detect before the test start. If there is no opening closing mechanism, the flammable samples are easy to burn too early. So this extra time is very important for the operator.

The sample holder -The sample size is 100mm x 100mm, and thickness is not exceed 50mm;The central portion of the sample about 50mm*50mm is exposed to the heating cone center and deviation is ±1%.

Weighting system -quality is measured by the strain gauge load cell test, accuracy up to 0.1g. Equipped with swift electronic weighing parts,mechanical stop fixture can avoid moving damage, to ensure the equipment longevity.Weighing range is 0 ~ 3kg.

Measurement

Paramagnetic oxygen analyzer, the range is 0-25%; linear response

With a laser system to measure the smoke density, using a photodiode, 0.5 mW helium-neon laser, primary and backup photodetectors. Also equipped with the positioning bracket and 0.3.0.8 neutral density filter used for calibration.

High-precision load sensor measures the weight changes of the test material during test process.The test range is 0~3000g, and resolution ratio is 0.01g. The required test sample weight is less than 500g.

Temperature control system: PID temperature control, 3 dia1mm thermocouples to measure temperature of the radiation cone, In addition with a 1 mm armoured thermocouple measuring the temperature 100mm above the orifice plate.

Exhaust flow: This data is caculated by the differential pressure of the sharp edge holes on both sides of the exhaust pipe,which inner dia is 57mm±1mm,and cooperate with micro differential pressure transmitter.Located at 350mm above fan transducer,the pressure transmitter is connected to the control system,so as to automatic control of wind speed.

Calibration

The United States imported Metherm thermopile type heat flow meter is used to set on the surface radiation level.Equipped with water cooling systemtoprotecting the security ofheat flow meter. - Design range is 0~100k W / m², the accuracy of heat flow meter is ±3%, repeatability is ±0.5%.

The burner correction system use purity of 99.5% methane to calibrate the instrument heat release rate; methane mass flow meter precise control of the flow of methane.

Equipped with a water cooling system for heat flow meter.

Equipped with a square calibration burner.

Operating

Labview control system, which easy to operate, and precise to control.It could show the apparatus status; Calibrate the device and store the results; Collect the test data; Calculate the necessary parameters; display results according to the requirements of standard; take the average value by multiple tests.

PC via RS485 interface communication module and PLC communication link for data transmission and motion control;

PID temperature control module and power adjustment module links, thermostatically regulated by a programmable controller;

Signal acquisition and processing module connected with the air volume control module circuit, output by a programmable logic controller,Intelligent adjust the preset speed.Mechanical rotating module links PLC I/O port, to control the closure of rotary.

The system provides query capabilities. The system automatically test sample number and temperature profile data stored in the database system;

Technical parameters

Conical heater rated power is 5000W, heat output is 0 ~ 100 kW / m2.

The sample weighing range is 0 ~ 3000g; precision is 0.1g.

Paramagn etic oxygen analyzer, the concentration range is 0~25%, an oxygen analyzer is linear response, Britain Servomex oxygen sensor; 10% to 90% response time of less than 12s; output noise does not exceed 50ppm;. Reproduce the measured values lower than 100ppm,

Infrared CO2 analyzer range: 0 to 10%; accuracy of ± 0.01%;

Exhaust fan flow 0 ~ 50g / s adjustable, precision 0.1g / s

The compressor works: cold trap: 0 to 5 degrees;

Import diaphragm pump, flow rate: 33 l / min

Thermopile type heat flow meter designed range 0 ^ 100k W / m², heat flow meter accuracy is ± 3%; repeatability is ± 0.5%

The standard detector color accuracy ± 5%, output linearity (transmission) <1%, absolute permeability <1%;

Qinsun Instruments Co., LTD is a professional laboratory testing instrument manufacturer in China,Have been focusing on laboratory instrument R&D more than 30 years and have rich industry experience,Based on international testing standards,We are also the instrument supplier for BV SGS laboratory,We provide one-stop solutions for lab instruments,Free Training and Turn-Key Service,Products exported all over the world,Offer 36 month warranty and are a trustworthy partner.


Send product request

To: Standard International Group (HK) Limited
Your E-mail:
Message text:


Send to other suppliers

Other supplier products

Bio-absorbable Internal Fixation Plates and Screws Test device
Bio-absorbable Internal Fixation Plates and Screws Test device Standard YY/T 0509-2009 (China): Specifies mechanical testing protocols for orthopedic plates/screws made of hydrolyzable polymers, including axia...
Sharp edge tester
Sharp edge tester Standards : ASTM F963 4.8. EN71-1998 8.14. GB6675-2003 A.5.9. 16CFR 1500.48 Basic Configuration: Sharp Edge Tester: 1 unit Foot switch: 1 set ...
Mining Cable Flame Resistant Apparatus,MT386
Mining Cable Flame Resistant Apparatus,MT386 Whats/App: +86 156 1874 6768 Web: standard-groups.com This tester is designed according to the standard MT 386-1995 "coal mine fire retardant cab...
Carpet tuft length measuring instrument
Carpet tuft length measuring instrument Standard BS 4223:1989 (British Standard): Specifies methods for determining the pile length of cut-pile carpets, ensuring consistency in quality...
Deval abrasion testing machine
Deval abrasion testing machine Product Introduction: Diphal abrasion testing machine is mainly used for stone abrasion rate test, suitable for European standards, French standar...
All supplier products

Same products

Adjustable flame length tester
Adjustable flame length tester Seller: Standard International Group (HK) Limited Whats/App: +86 156 1874 6768 Web: standard-groups.com Standard GB/T 5169.5: Electrical & E...
Fabric Flame Retardant Tester
Fabric Flame Retardant Tester Seller: Qinsun Instruments Co., LTD Product details A method is used to determine the damaged area and the length of the damage when...
Burning Manikin System
Burning Manikin System Seller: Qinsun Instruments Co., LTD Product details The burning manikin system is used to test the overall thermal protection perfor...
Steel Structure Fireproof Coatings
Steel Structure Fireproof Coatings Seller: Qinsun Instruments Co., LTD Product Introduction: Heat insulation efficiency and fire resistance test furnace of steel struc...
Building material combustion calorific value calorimeter
Building material combustion calorific value calorimeter Seller: Qinsun Instruments Co., LTD Product details Building material combustion calorific value calorimeter Mainly used for the det...