11KV SF6 Gas Load Break Switch

The FWX1-12/630 outdoor SF6 load break switch is suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and the rated frequency 50/60Hz, which can break off and close the load current and overload current in the power system. The load switch is equipped with an intelligent controller to realize the automation of the distribution system.

Features of 12KV SF6 Gas Load Break Switch

The operating mechanism with spring energy storage ensures fast closing and switching operation (<1000ms).

Operator place: Local/Remote.

Equipped with an electronic controller, it can be operated locally or with FTU/RTU interface for console operation.

Specification of 11KV SF6 Gas Load Break Switch

Parameter Name

Unit

Technical Requirement

Rated Maximum Voltage

kV

12

Rated continuous Current

A

630

Short Time Withstand Current

kA

20

Short-circuit Making Current (peak)

kA

50

Power Operating Time (Close/Open)

sec

<2

Mechanical Operations

times

3000

Rated full load operations

times

400

Breaking Capacity

Main Active (0.7pf)

A

630

Cable charging

A

5

Transformer magnetizing

A

10

Lightning Impulse Withstand Level

Phase to Earth

kV

75

Across interrupter

kV

85

Power Frequency withstand voltage

Phase to Earth

kV

42

Across interrupter

kV

50

Other Ratings & Specifications

Creepage Distance (Silicon)

mm

830

IP Level

65

Arc Extinction Medium

SF6 Gas

Insulation Medium

SF6 Gas

Leakage Rate

cc/ sec

≤0.5%

Product size (max)

Width

mm/in

1368/54

Height

mm/in

530/21

Environmental Conditions for Equipment Use

Environmental conditions for equipment use

  1. :≤3000m
  2. : -40℃~+50℃

Maximum diurnal temperature difference:≤25℃

  1. :Daily mean95% monthly average90%
  2. :≤34m/s
  3. :<8 degree
  4. <10mm
  5. <35mm
  6. <0.1W/cm2

Working Procedure of 11KV SF6 Gas Load Break Switch

The load switch that uses SF6 gas as insulation and arc extinguishing medium is called the SF6 load switch. It can be used to switch and switch load current and overload current, and it can also be used to switch and switch no-load circuits, no-load transformers, and capacitors. Groups, etc., all three-position load switches with the functions of connecting, disconnecting, and grounding have the characteristics of simple structure and low price. But the load switch cannot disconnect the short-circuit current.

Intended Use of 11KV SF6 Gas Load Break Switch

The SF6 load switch is an excellent load switch that many users have experienced in recent years. In addition to its long electrical life and strong braking force, it has the same advantages as the vacuum load switch. Its outstanding advantage is that it is easy to achieve three working positions (connected, disconnection and grounding), small current (inductance, capacitance) breaking, strong resistance to severe environmental conditions. It is suitable for popularization and application in urban and rural medium voltage distribution networks.

Zhuhai GopowerSmart Grid Co., Ltd. is one of the earliest electric power equipment company. We provide 11kv lbs,11kv load break switch, load break switch 11kvand etc. Want to know 11kv load break switch priceor more? Please contact us.


Send product request

To: Zhuhai Gopower Smart Grid Co; LTD
Your E-mail:
Message text:


Send to other suppliers

Other supplier products

SF6 Gas 11KV Load Break Switch
SF6 Gas 11KV Load Break Switch Theload break switch11kvis suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and the rated frequency 50/...
33KV Vacuum Circuit Breaker
33KV Vacuum Circuit Breaker Breaker Switch Unit with Encapsulated Vacuum Interrupter Each 33kv automatic circuit recloseris embedded in a solid-insulated pole made of weather...
Pole Mounted Switch
Pole Mounted Switch The pole mounted disconnect switchis a kind of safety switch used on the electric pole to ensure the safety of electricity. Its main function is to...
33KV SF6 Gas Load Break Switch
33KV SF6 Gas Load Break Switch 33KV SF6 Gas Load Break Switch These load break switch 33kv are intended for outdoor applications. They can be mounted either horizontally or verti...
Centralized Type DTU
Centralized Type DTU Centralized Type DTU The centralized DTU adopts high-performance MCU processor, high-speed industrial network communication technology, multi-CPU ...
All supplier products

Same products

Microcrystalline wax used for rubber plastic processing and modification
Microcrystalline wax used for rubber plastic processing and modification Seller: Syntop chemical Co.,Ltd. Microcrystalline wax has a wide range of industrial applications, primarily in the areas of rubbe...
Microcrystalline wax 80A used for lubrication and demolding
Microcrystalline wax 80A used for lubrication and demolding Seller: Syntop chemical Co.,Ltd. The core industrial applications of microcrystalline wax 80A are primarily focused on rubber prot...
Tyvek Flat Roll Pouch
Tyvek Flat Roll Pouch Seller: Hopeway AMD Tyvek Flat Roll Pouch is designed for professional sterilization packaging, offering clean handli...
Industrial Warehouse Ceiling Fans
Industrial Warehouse Ceiling Fans Seller: Hebei Windmax Power Technology Co., Ltd. Industrial Warehouse Ceiling Fans Industrial Warehouse Ceiling Fans for Warehouses, Logis...
HVLS Ceiling Fan for Railway Station
HVLS Ceiling Fan for Railway Station Seller: Hebei Windmax Power Technology Co., Ltd. HVLS Ceiling Fan for Railway Station for Railway Station All units are CE-certified, manufa...