24KV Recloser Vacuum Circuit Breaker
The 24KV breaker switch unit is comprised of three poles, the operating mechanism, and the operating mechanism housing. The sequence of the poles is A -B – C or 1 – 2 - 3 (sequence left to right when viewed from the lower terminal side of the recloser switch unit.
Each 24kv vacuum circuit breakerby GOPOWERis embedded in a solid-insulated pole made of weather-proof cyclo aliphatic epoxy resin. This enables a small design as well as resistance against environmental effects.
Breaker principle and design of 24KV Vacuum Circuit Breaker
ZW32 series 24KV circuit recloser are used in distribution systems. 24kv vacuum circuit breakes are used to make and break normal and fault currents. Breakers are fully equipped with sensors and a controller to provide a means of protection and control.
In case of a line fault, breakers can break and make currents several times, thus avoiding longer network interruptions due to temporary faults. The manufacture, design, and testing of the vacuum recloser is based on current standards IEC 62271-111:2019
Technical Parameters of 24KV Vacuum Circuit Breaker
|
Products Type |
ZW32-24 |
|
Maximum System Voltage |
24kV |
|
Rated Continuous Current |
630A |
|
Rated Frequency |
50/60Hz |
|
Short Time Withstand Current |
20kA/1sec |
|
Mainly Active Load Current |
630A |
|
Number of Load-break Operations |
30 |
|
Short-circuit Making Current (peak) |
50kA |
|
Number of Making Operations |
5 times |
|
Cable Charging Current |
25A |
|
Line Charging Current |
|
|
Closed Loop Circuit Current |
630A |
|
Transformer Magnetizing Current |
22A |
|
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters |
50kV |
|
DryCondition-1min,Ph- Ph, Phase to Earth |
65kV |
|
Dry Condition - 1 min AcrossInterrupter |
79kV |
|
Phase to Phase, Phase to Earth |
125kV |
|
Across Interrupter |
145kV |
|
Internal Arc Test |
20kA /0.1 sec |
|
Arc Extinction Medium |
vacuum |
|
Insulation Medium |
vacuum |
|
Creepage Distance (Silicon) |
960mm |
|
Dry arcing distance |
200mm≥ |
|
IP Level |
67 |
|
Closing/Opening Time |
<1sec |
|
Mechanical Operations (Guaranteed) |
10000times |
|
Operating Temperature (*Manual Type) |
-25~+70℃ |
Gopower is a professional electric power equipment company, we provide auto recloser, load break switchand etc. For more info, please feel free to contact us!
Send product request
Other supplier products
| 24KV Recloser Vacuum Circuit Breaker | The 24KV breaker switch unit is comprised of three poles, the operating mechanism, and the operating mechanism housing. The sequence of the poles i... | |
| 15KV SF6 Gas Load Break Switch | 15 kv pole mounted disconnect switch is suitable for rated voltage 15kV, rated current 630A, 50/60Hz distribution network breaking. The load curren... | |
| SF6 Gas 11 KV Load Break Switch | The 11 kv load break switchis suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and the rated frequency ... | |
| SF6 Gas Load Break Switch 11kv | The 11 kv load break switch is suitable for the distribution network with the highest voltage 11kV, the rated current 630A, and the rated frequency... | |
| 24KV Vacuum Circuit Breaker | Each vacuum interrupter is embedded in a solid-insulated pole made of weather-proof cyclo aliphatic epoxy resin. This enables a small design as wel... |
Same products
| pet toys | Seller: Zhangjiagang Kingtale International Co., Ltd. | Wholesale Durable Pet Toys | |
| pet toys | Seller: Zhangjiagang Kingtale International Co., Ltd. | Wholesale Durable Pet Toys | |
| ApsNesswell Histology Cassette Printer,4 Slot Tissue Cassette Printer | Seller: Shenyang Aps Nesswell Technology Co.,Ltd | ApsNesswell Histology Cassette Printer,4 Slot Tissue Cassette Printer Our histology cassette pri... | |
| ApsNesswell Automatic Slide Stainer,H&E Stainer | Seller: Shenyang Aps Nesswell Technology Co.,Ltd | ApsNesswell Automatic Slide Stainer,H&E Stainer One of the most trusted equipment in your la... | |
| ApsNesswell Carousel Tissue | Seller: Shenyang Aps Nesswell Technology Co.,Ltd | ApsNesswell Carousel Tissue Processor,Automatic Tissue Processor APS-6A&6B rotary or carouse... |