KELLER pressure water level sensor

Uses: The input capacitance transmitter is used for water level measurement.
Principle: The 46X pressure sensor is composed of a ceramic measuring element suitable for low pressure measurement and the uP electronic part of the 30 series digital transmitter. The pressure value is formed after polynomial compensation according to the signals sent by the pressure and temperature sensors. This value can be displayed or stored on the computer via the RS485 interface, and can also be programmed. A reference tube integrated in the cable connects the sensor reference cavity to the atmosphere.
Technical specifications:
Pressure range (FS)
30 100 300 mbar
Overpressure
300 1000 1500 mbar
Types of
2-wire system
3-wire system
Power supply (U) 46X
8…28VDC
13…28VDC
Power supply (U) 46XEi
10…30VDC
15…30VDC
output signal
4…20mA
0…10V
Load
<(U-8V)/0.02A
>5K
stability
+0.1%FS (FS>=100mbar)
+0.1mbar(FS<100mbar)
Operating temperature
0…80 degrees Celsius
Compensation temperature
10…50 degrees Celsius
Error interval**
Typical +0.1%FS, maximum +0.2%FS
Wire type
5.8mm (PE) with vent tube inside
cable length
5m standard
Wetted material
-Housing: stainless steel (standard AISI316L)
-Diaphragm: ceramic, gold-plated
Neoprene O-ring
Protection class
IP68
weight
400g (including 5m cable)
Origin: Switzerland
Other supplier products
|
|
SO-421 soil oxygen sensor |
用途:SO-421的响应时间快,为14秒,专为实验室应用而设计。它配有一个用于校正温度变化的热敏电阻温度传感器和一个电阻加热器,可将膜的温度提高到环境温度以上约2度,以防止聚四氟乙烯膜上发生冷凝并阻挡传感器的扩散路径。典型应用包括在实验室实验中测量O 2,监测室内环境中的气态O 2以进行气候控... |
|
|
QT-TQ0402 TRIME probe installation tool kit |
Product description: QT-TQ0402 probe installation tool kit can be used for the installation of plastic transparent access tube (outer diameter 44mm... |
|
|
SI-111 infrared surface temperature sensor |
SI-111 consists of a thermopile and a thermistor. The thermopile measures the surface temperature and the thermistor measures the body temperature ... |
|
|
105E Thermocouple Sensor |
105E is a commonly used shielded No. 24 type E thermocouple, which is suitable for measuring soil temperature and the temperature of similar enviro... |
|
|
CS10-L current transmitter |
Introduction: The CS10 current transmitter monitors the DC current along a single wire from 0.15 A to 200 A. Its output is a millivolt signal, suit... |
All supplier products
Same products