15KV SF6 Gas Load Break Switch
15KV SF6 Gas Load Break Switch
15 kv pole mounted disconnect switch is suitable for rated voltage 15kV, rated current 630A, 50/60Hz distribution network breaking. The load current or overload current in a power system automatically isolates the faulty sections of the distribution line.
With the latest technology electronic controller, this manual load break switch realizes manual operation, electric operation, and remote operation. The electronic controller is installed in the stainless steel box and can be used under various climatic conditions. In addition, 15kv load break switchcable and wireless modems can be installed in the box to realize remote monitoring and control. Simple installation and arrangement on the pole are convenient, quick, and low construction cost.
Characteristics of 15KV SF6 Gas Load Breaker Switch
The 15KVpole mounted disconnect switchis made of proven durable, corrosion-resistant material. (304L stainless steel plate for warships), ensure a long service life (30years), our 15kv load break switch can carry out a series of operations, with the pole top equipment ideal characteristics.
EachGOPOWER 15kv load break switch has been filled with sf6 gas before leaving the factory, sealed treatment. The 15 kv pole mounted disconnect switch test was carried out according to IEC60265-1 (1988) GB 3804-1990 standard.
SF6 Load Break SwitchIn Pole Mounted Switch Solution
15kv load break switch has a certain interrupting capacity because of the interrupting device, but 15 kv pole mounted disconnect switch is not as strong as the interrupting capacity of the circuit breaker, which can split the normal working current, and in the case of short circuit, he can only silently withstand the short circuit current, and if this time the manual or electric breaking may explode, so the load switch is generally used together with the current limiting fuse (load switch + fuse is not the standard configuration, and can also be used without fuse) In the event of an overload or short circuit, the circuit is broken by a fuse. In order to save costs, the load switch + fuse can replace the circuit breaker. Inquiry more pole mounted switch solutions
Specification of 15 KV Pole Mounted Disconnect Switch
Products Type |
FWX-15 |
Basic Ratings |
|
Maximum System Voltage |
15KV |
Rated Continuous Current |
630A |
Rated Frequency |
50/60Hz |
Short Time Withstand Current |
IKA/sec |
Making and Breaking Capacity |
|
Mainly Active LoadCurrent |
630A |
Number of Load-break Operations |
400times |
Short-circuit Making Current(peak) |
50K |
Number of Making Operations on 15 KV Pole Mounted Disconnect Switch
Number of Making Operations |
5 times |
Cable Charging Current |
loudspeaker |
Line Charging Current |
loudspeaker |
Closed Loop Circuit Current |
630A |
Transformer Magnetizing Current |
22A |
Power Frequency Withstand Current Test |
|
Wet Condition- 10 sec (Ph- Ph-Eth, Across Interrupters) |
50KV |
DryCondition- I min ( Phase to Phase, Phase to Earth) |
50KV |
Dry Condition - 1 min (Across Interrupter ) |
60KV |
Impulse Withstand Current Test(1.2 x 50 s) |
Internal Arc Test of 15 KV Pole Mounted Disconnect Switch
Internal Arc Test |
20kA / 0.1 sec |
Arc Extinction Medium |
SF6 Gas |
Insulation Medium |
SF6 Gas |
Creepage Distance (Porcelain) |
560mm |
IP Level |
54 |
Operation Performance |
|
Closing/Opening Tin |
< O. l sec |
Mechanica l Operations (Guaranteed) |
l OOOO times |
Operating Temperature.1re(*Manual Type) |
-25~+70℃ |
Gas Pressure |
|
Nominal Pressure (kg/cm2 G, at 20°C) |
|
Bursting Pressure (kg/cm2 G) |
4 ~ 6 |
Minimum Gas Pressure (kg/cm2 G) |
0 |
Leakage Rate (cc/ sec) |
1% |
Other Ratings & Specifications of 15 KV Pole Mounted Disconnect Switch
Other Ratings & Specifications |
|||
Internal Arc Test |
20kA / 0.1 sec |
20kA / 0.1 sec |
20kA / 0.1 sec |
Arc Extinction Medium |
SF6 Gas |
SF6 Gas |
SF6 Gas |
Insulation Medium |
SF6 Gas |
SF6 Gas |
SF6 Gas |
Creepage Distance (Porcelain) |
380mm |
700mm |
1055mm |
Creepage Distance (Silicon) |
780mm |
1200mm |
1550mm |
Dry arcing distance |
≥200mm |
≥ |
≥ |
IP Level |
65 |
65 |
65 |
Operation Performance |
|||
Closing/Opening Time |
1sec |
1sec |
1sec |
Mechanical Operations (Guaranteed) |
10000times |
10000times |
10000times |
Operating Temperature (*Manual Type) |
-25~+70℃ |
-25~+70℃ |
-25~+70℃ |
Gas Pressure |
|||
Nominal Pressure (MPa, at 20°C) |
|||
Bursting Pressure (MPa) |
|
||
Minimum Gas Pressure (MPa) |
|||
Leakage Rate (cc/ sec) |
≤0.5% |
≤0.5% |
≤0.5% |
Voltage sensors |
|||
CT ABC 10P10 5VA |
400:05:00 |
400:05:00 |
400:05:00 |
Incoming side and outgoing side of the voltage sensor |
6 Voltage sensor(built-in) Phase voltage:(24(36)kV/√3)/(3.25V/√3) |
||
Special attention should be paid to the voltage sensor, which must be directly fed by the 15kv load break pole mounted disconnect switch. No additional adjustment circuit can be added to the controller. The voltage signal of the switch into the test line needs to be tested separately. |
Gopowerattaches great importance to the improvement of enterprise research and development ability. It invests no less than 8% of annual sales in product research and development every year, and its r&d technicians account for more than 30% of the total number of the company. We have a well-equipped, experienced, professional, dedicated and stable r&d technical team, and cooperate with south China University of Technology, Sun Yat-sen University, Beijing Institute of Technology and other domestic universities to jointly carry out research on the application and future direction of products in the field of smart distribution network, Our pole mounted disconnect switch such as11kv lbs,15 kv pole mounted disconnect switch,feeder terminal unithave always been dedicated to providing customers with stable and reliable overall solutions for smart distribution networks with a professional spirit.
在线联系供应商
Other supplier products
LBS 24KV 630a SF6 Gas Load Break Switch | 24kV SF6 load break switch is a switch equipment for medium voltage switchgear, using SF6 gas as arc extinguishing and insulating medium. Rate volt... | |
VCB Pole Mounted Recloser | ZW32 series automatic circuit line recloser, produced by our vacuum circuit breaker company, are used in distribution systems. Auto distribution li... | |
Centralized Type DTU | The centralized DTU adopts high-performance MCU processor, high-speed industrial network communication technology, multi-CPU integration technology... | |
Recloser Control Box-Feeder Terminal Unit | Recloser Control Box-Feeder Terminal Unit The feeder terminal unit(FTU) is a new HV switch control device of control cabinet enclosures equipped w... | |
24KV SF6 Gas Load Break Switch | Application of 24KV SF6 Gas Load Breaker Switch The SF6 lbs 24kv 630agas-insulated switch is a three-phase interoperable switching device design... |
Same products
Temperature Controller | 卖方: Tinko Instrument (Suzhou) Co., Ltd. | Tinko temperature controller industrialcan improve process efficiency, product quality and minimi... | |
Sequence Valve Gate Controller | 卖方: Tinko Instrument (Suzhou) Co., Ltd. | Tinko hydraulic valve gate controllerenables control of valve gate flow sequence and timing for p... | |
TSC-02 Stand Alone Controller | 卖方: Tinko Instrument (Suzhou) Co., Ltd. | Tinko TSC-02 integrated dual zone temperature controlleris suitable for small mold. The portable ... | |
TSC-01 Stand Alone Controller | 卖方: Tinko Instrument (Suzhou) Co., Ltd. | Tinko TSC-01 integrated single zone hot runner temperature controller is suitable for small mold.... | |
Touch Screen Hot Runner Controller | 卖方: Tinko Instrument (Suzhou) Co., Ltd. | M20 series touch screen hot runner temperature controllers are newly developed with latest achiev... |