AC gapless metal oxide arrester
AC gapless metal oxide arrester
AC gapless metal oxide arrester (hereinafter referred to as arrester) is used to protect AC electrical equipment of corresponding voltage level from lightning overvoltage and operating overvoltage damage.
Product Implementation Standard: GB11032 - 2010 "AC electrical equipment arrester".
7Earthquake intensity 8 degrees and below;
This kind of arrester is assembled by superposition of non-linear zinc oxide resistors and sealed in high voltage insulating ceramic sleeve without any discharge gap.Under normal operating voltage, the arrester is insulated with high resistance; when it is impacted by overvoltage, the arrester is in low resistance state, releasing impulse current into the ground quickly, so that the voltage on the electrical equipment parallel to it is limited to the prescribed value, so as to ensure the safe operation of the electrical equipment.The arrester is equipped with a detachment device. When the arrester operates under overload or suffers accidental damage, the internal pressure increases sharply, so that the arrester can be detached from the device to ensure that the ceramic sleeve is not damaged.The arrester has the characteristics of good steep wave response, high shock current tolerance, low residual voltage, reliable operation, no power frequency continuous current, simple maintenance and so on.
Sex testing tests, the items are:
(1) DC or power frequency reference voltage test:
When the peak value of DC or AC resistive current flowing through the arrester reaches the reference current, read the voltage value, which is not less than the standard value.
(2) DC leakage current test:
The DC voltage value of 0.75U1mA is applied at both ends of the arrester (the voltage ripple rate is not more than (+1.5%). When the voltage is stabilized, the leakage current flowing through the arrester should not be greater than the standard value. The leakage current of the surge arrester in operation should be no more than 2 times of the measured value before commissioning.
(3) Detection of power frequency persistent current value:
Power Frequency Continuous Current Value, Leakage Current Tester or Sufficient for Use of Arresters
Accurate AC meter detection shows that the RMS or peak resistance current flowing through the arrester under operating power frequency voltage does not exceed 1.5 times of the initial measurement value.
Ⅵ. Attention:
(1) During transportation and storage, arresters should be placed vertically.
(2) Users are not allowed to disassemble lightning arresters at will.
(3) Users are not allowed to test the working frequency discharge voltage of the arrester in order to avoid damage to the arrester.
(4) Under the condition that users abide by the above rules, our factory is responsible for the three-package matters within the three-package period, which is one year.
If users have special needs, they can write to them. We will supply as required.
The company mainly product are low voltage switch cabinet, frequency converter cabinet. And we undertake various one-stop services such as preliminary exploration, design, survey, construction, manufacturing, operation and maintenance.
Send product request
Other supplier products
WSD-ZW32-24GD Outdoor AC high voltage vacuum circuit breaker | WSD-ZW32-24GD Outdoor AC high voltage vacuum circuit breaker Overview WSD-ZW32-24GDOutdoor AChigh voltage vacuum circuit breaker(hereinafter referr... | |
(H) RW 12-24 Outdoor High Voltage Drop Fuse | (H) RW 12-24 Outdoor High Voltage Drop Fuse (H) RW 12-27 drop fuse and pull-load drop fuse are outdoor high-voltage protective appliances, which ar... | |
WSD-ZW32-24D Outdoor AC high voltage vacuum circuit breaker | WSD-ZW32-24D Outdoor AC high voltage vacuum circuit breaker Overview WSD-ZW32-24DOutdoor AC high voltage vacuum circuit breaker (hereinafter referr... | |
AC gapless metal oxide arrester | AC gapless metal oxide arrester AC gapless metal oxide arrester (hereinafter referred to as arrester) is used to protect AC electrical equipment of... | |
XL-21 low-voltage power distribution cabinet | XL-21 low-voltage power distribution cabinet Overview XL-21 Low Voltage Switch Cabinetis suitable for power plant, industry and mining enterprises.... |
Same products
4rb 210-0ah16-7 Side Channel Blower/Regenerative Blower | Seller: Greentech International (Zhangqiu) Co., Ltd | Greentech International (Zhangqiu) Co., Ltd is the professional side channel blower supplier.The ... | |
4rb 310-0ah26-7 Ring Blower Side Channel Blower for Waste Water Treatment | Seller: Greentech International (Zhangqiu) Co., Ltd | Greentech International (Zhangqiu) Co., Ltd is the professional side channel blower supplier.The ... | |
4rb 410-0ah16-7 Side Channel Blower/Electric Blower | Seller: Greentech International (Zhangqiu) Co., Ltd | Greentech International (Zhangqiu) Co., Ltd is the professional side channel blower supplier.The ... | |
4rb 510-0ah26-8 Side Channel Blower/Air Compressor | Seller: Greentech International (Zhangqiu) Co., Ltd | Greentech International (Zhangqiu) Co., Ltd is the professional side channel blower supplier.The ... | |
4RB 610-0AH36-8 Regenerative Blower/Air Compressor/Regenerative Blower | Seller: Greentech International (Zhangqiu) Co., Ltd | Greentech International (Zhangqiu) Co., Ltd is the professional side channel blower supplier.The ... |