DW45 Air Circuit Breaker
Scope of application
DW45 Air Circuit Breaker, ACB (hereinafter referred to as circuit breaker) is suitable for distribution network with AC 50Hz, rated voltage to 660V (690V) and below, the rated current 630A~6300A, used to distribute power and protect line and power equipment from overload, undervoltage, short circuit, single-phase grounding and other faults. Air Circuit Breaker have intelligent protection function, selective protection is precise, can improve power supply reliability and avoid unnecessary power outages. At the same time, it has an open communication interface to carry out "Four Remotes" to meet the requirements of the control center and automation system. The circuit breaker has an impulse withstand voltage of 8000V at 2000 meters (revised at different altitudes, not exceeding 12000V). The acb air circuit breaker are not equipped with intelligent controller and sensor, and can be used as isolator.
TAIXI is a professional air circuit breaker manufacturers The acb air circuit breaker meets the GB14048.2 "Low-voltage switchgear and controlgear Low-voltage circuit breakers" and IEC60947-2 "Low-voltage switchgear and controlgear circuit breakers" and other standards.
Normal working conditions and installation conditions
● Ambient air temperature: The upper limit value does not exceed +40°C, the lower limit value is not less than -5°C, and the average value in 24h does not exceed +35°C. Note: The working condition is that lower limit value is -10°C or -25°C, the user should declare with the company; The upper limit exceeds +40°C or the lower limit is lower than -10°C or -25°C working conditions, users should consult with the company.
● The altitude of the installation site does not exceed 2000m.
● Atmospheric conditions of Air Circuit Breaker: Atmospheric relative humidity does not exceed 50% when the ambient air is +40°C. It can have relatively high relative humidity at lower temperatures. The monthly average maximum relative humidity of the wetest month is 90%. The average minimum temperature is +25°C and consider the condensation that occurs on the product surface due to temperature changes. Exceed the required requirements and consult with the company.
● Protection level: IP30
● Pollution level: III
● Use category: Class B or Class A
● Installation category: acb air circuit breaker and undervoltage release with rated operating voltage of 660V (690V) or less. The primary coil of the power transformer is used for installation category IV. The installation category of the auxiliary circuit and control circuit is III.
● Installation conditions: The circuit breaker shall be installed in accordance with the requirements of this manual. The vertical inclination of the circuit breaker shall not exceed 5° (the inclination of the mine circuit breaker shall not exceed 15°).
Other supplier products
|
TXDL18-63 Residual Current Circuit Breaker |
Scope of Application TXDL18-63 Residual Current Circuit Breakers are widely used in domestic and foreign industrial, commercial and civil construct... |
|
HG2B In-line Fuse Switch Disconnector |
Scope of application HG2B In-line Fuse Switch Disconnector is suitable for AC rated voltage 660V and below, AC 160A~630A, rated AC frequency 50Hz. ... |
|
DZ15LD Molded Case Circuit Breaker |
Scope of Application DZ15LD Molded Case Circuit Breaker is a circuit breaker with three lights display to indicate default phase, over-current, fau... |
|
TDGC2 Single Phase Voltage Regulator |
Product Overview TDGC2 Single Phase Voltage Regulator is an adjustable autotransformer structure; The coil is wound evenly around the ring-shaped i... |
|
TXC65-63 Miniature Circuit Breaker |
Scope of ApplicationTXC65-63 Circuit Breaker is used for the circuit of AC 50Hz, rated voltage of 110V/230/400V, rated current of 63A to protect ov... |
All supplier products
Same products