HYPCIT Primary current injection tester
Introduction:
HYPCIT series primary current injection tester is applied in power system for circuit breaker test, protection system test and current transformer test. The current injection tester generates a high current from power supply to simulate the rated current or fault current in the primary circuit of power equipment.
Applications:
1)High current output injected to the main circuit of power line to simulate the fault current. And then check whether the protection system will be operated according to the design
2) High current output injected to the primary of current transformer and then measure the inducted current from secondary by error measurement instrument to check the ratio error and phase displacement of CT
3)High current output injected to the main circuit of circuit breaker to simulate the rated current in primary. And then check the stability of circuit breaker according to the temperature rise procedure.
4)Considered as a AC high current source in power equipment or cable test.
Primary current injection tester technical index:
1 Power supply: AC220V or AC 400V, 45Hz~65Hz. The power supply voltage is depends on the power output capacity. Detail information is as table 1.
2 Typical output current: 500A or 1000A or 2000A
Typical output capacity 3KVA or 5KVA or10KVA or15KVA
It can be customized according to your requirements from above specs
3 Impendence voltage: 8%
4 Idle current: 6%
5 Current distortion <5%
6 Current is measured from the secondary of current transformer which is installed in the internal of the current booster. The display unit is 4 and 1/2 digitals current meter. Maximum measurement error 0.5%RDG+5D.
7 Timer indication of test running is an optional configuration. The timer could be customized according to the requirement of customer from the follow list:
1) 4 digital timer from 0~9999s / 0~999.9s /0~99.99s, accuracy 0.5%RDG+5D
2) 5 digital timer from 0~99999s / 0~9999.9s /0~999.99s, accuracy 0.2%RDG+2D
3) 6 digital timer from 0~999999s / 0~99999.9s /0~9999.99s, accuracy 0.1%RDG+1D
8 work temperature:0~40 C, Humidity <90%
Model |
Output Current (A) |
Capacity (KVA) |
Output Voltage (V) |
3/500 |
500 |
3 |
6 |
5/500 |
500 |
5 |
10 |
10/500 |
500 |
10 |
20 |
15/500 |
500 |
15 |
30 |
3/1000 |
1000 |
3 |
3 |
5/1000 |
1000 |
5 |
5 |
10/1000 |
1000 |
10 |
10 |
15/1000 |
1000 |
15 |
15 |
3/2000 |
2000 |
3 |
1.5 |
5/2000 |
2000 |
5 |
2.5 |
10/2000 |
2000 |
10 |
5 |
15/2000 |
2000 |
15 |
7.5 |
Email
Miss Chloe Wang
Send product request
Other supplier products
All supplier products
HYYJ-501 insulating oil tester
Dielectric oil tester functions:
1 Breakdown test of user-defined2 Proof test3 Calibration interface for customers4 Uploading data to PC and making...
HY2303 Insulation Tester
Rated Voltage
2500V
5000V
10000V
Measuring Range
0.0~99.9MΩ100~999MΩ1.00~9.99GΩ10.0~100GΩ
0.0~99.9MΩ100~999M&O...
HYZC series winding resistance tester
Winding resistance testerintroduction
There are four DC currents to select for HYZC-20 which has a large output power,
the power of the tester itse...
HYJB-PC6 6 Phase Relay Tester
6 Phase Relay Tester
This tester with standard 6 phase voltage, 6 phase current output, voltage 125V/phase, current 30A/phase, 6 phases in parallel...
HY2305 Insulation Tester
Insulation Tester HY2305
RatedVoltage
250V
500V
1000V
2500V
5000V
Measuring Range
0.0~99.9MΩ100~999MΩ1.00~10.0GΩ
0.0~99.9...
Same products
Bently Nevada AC Power Supply PN 127610-01 of 3500/15
Seller: 840499
3500/15 127610-01 | Bently Nevada | 3500/15 交流电源模块(停产。新替代品:106M1079-01:通用交流电源模块)3500/15 127610-01...
Tunnel special box transformer
Seller: 839459
Tunnel special box transformer is a product specially designed for use in the tunnel environment....
AC Metal Аrmored Movable Switchgear 35KV KYN40.5 in-hous
Seller: 839459
KYN61-40.5 armored movable AC metal enclosed switchgear is suitable for three-phase AC 50Hz power...
Аctive Filter Cabinet
Seller: 839459
Аctive filter: сollaborating with well-known component manufacturers in the industry to provide h...
SVG
Seller: 839459
SVG: ensuring electricity safety, passing national testing standard.