TXCM1LE Molded Case Circuit Breaker

Scope of Application
TXCM1LE Molded Case Circuit Breaker is one of the new breakers which have been designed and developed by the company using international advanced technology. Suitable for the circuits of AC 50Hz, rated voltage of 400V, rated current of 16A to 800A.
Its main function is to provide indirect contact protection for personal electric shock of fatal danger. Rated residual operating current does not exceed residual current operated circuit breaker of 0.03A when other protection measures are invalid, also can provide supplementary protection for direct contact, but not as the only direct contact protection. At the same time, CM1LE MCCB can also prevent electrical fire caused by the contact fault current. And CM1LE MCCB can protect overload and short circuit of the circuits, can also be used for infrequent conversion of the circuits.
TXCM1LE MCCB can be mounted vertically (upright) or horizontally (transverse).
Meet the standards: GB 14048.2, IEC 60947-20
Normal operating conditions and installation conditions
Ambient air temperature
The upper limit of ambient air temperature is +40℃;
The lower limit of ambient air temperature is -5℃;
The average value of ambient air temperature within 24h does not exceed +35℃.
Altitude: The altitude of the installation site is not more than 2000m.
Pollution degree: 3.
Installation category: III.
Atmospheric conditions: The air relative humidity in the highest temperature + 40℃ for not more than 50%; In the low temperature can have higher relative humidity. The maximum average relative humidity is 90%, while the average monthly minimum temperature is +20℃, and consider the temperature changes in product on the surface of the gel.
External magnetic field: The external magnetic field in the vicinity of the installation site does not exceed 5 times the geomagnetic field in any direction.
Другие товары поставщика
|
|
TXCM1E |
Scope Of Application TXCM1E lv Current adjustable circuit breaker (hereinafter referred to as circuit breaker), the circuit breaker has small size,... |
|
|
WCT Din Rail Mounted Contactor |
Scope of Application WCT Din Rail Mounted Contactor (also called CT contactor, household Contactor), mainly used in power system of AC 50Hz/60Hz, r... |
|
|
TXSPD Surge Protection Device |
Scope of Application TXSPD Surge Protection Device is used for power supply systems of AC 50/60Hz, rated voltage 380V and below, to protect the pow... |
|
|
TDGC2 Single Phase Voltage Regulator |
Product Overview TDGC2 Single Phase Voltage Regulator is an adjustable autotransformer structure; The coil is wound evenly around the ring-shaped i... |
|
|
TXDL18-63 Residual Current Circuit Breaker |
Scope of Application TXDL18-63 Residual Current Circuit Breakers are widely used in domestic and foreign industrial, commercial and civil construct... |
Все товары поставщика
Похожие товары