Shielding hall of HV PD test

Shielding hall of HV PD test

Application:

HV test shielding room (faraday cage) areWidely used in power cable, transformer, transformer switch, transformer substation and other High voltage levels of partial discharge test or impulse test.

For HV testing shielding room, as a HV test place, it should has good electromagnetic

shielding condition. And its electromagnetic compatibility always is of great importance.

Firstly, it should restrict electromagnetic wave into inside shielding room caused by

discharge when making HV test to weakening interfere to outside, especially on

electronic and communication system. Secondly, it should prevent outer

electromagnetic wave intruding into shielding room to cause measurement error of

partial discharge and wireless. Thirdly, it should reduces open circuit voltage and

closed current to restrain common-mode interference so that to avoid equipment

damage and to improve accuracy of impulse measurement.

For GIS HV test shielding room, design area is 500 m2(Length 25m、Width 20m).

From provided information , we find that steel structure have been completed

already with one set of 20T crane indoor, crane supporting corbel also completed, the

height is 17.9m from ground to upper part of corbel. Main door height 13m,width 10m,

locates at downward of the west side, the door open direction towards to north .

According to ILJIN drawing, three side of structure column has already, but western

structure column still missing yet. however, as the main door will be located in this side,

the western side also should have steel structure , and this structure position still should

be unified considered with main door installation. We will be able to submit suggested

design diagram with position & size of this structure column for reference. in order to

save construction cost, the construction engineering will be carried out by ILJIN

Technical Specification

 Shielding efficiency 0.15 MHz~1.6MHz≥60dB

 reverberation time <5S(at 400Hz 400Hz )

 Background noise level (Ambient level) <5Pc

 Grounding resistance :≤0.5Ω

Background noise can be promised to be not more than 5Pc if no-load equipment

without voltage. (this is what we should to ensure).

 Under equipment running condition ( applied voltage on equipment), user

should check on the whole testing system. such as whether power frequency

testing transformer meets with ambient requirements or not? whether if power

supply has been treated well or not? Whether surrounding other equipment are

placed too close to cause interference or not? And so on. To be honest, And it

seems not directly relevant to background noise level of shielding room .



在线联系供应商

至: CNME Intermational Co.Ltd
Your E-mail:
消息正文:


Send to other suppliers

Other supplier products

Partial Discharge Testing Detector Testing instrument
Partial Discharge Testing Detector Testing instrument Partial Discharge Testing Detector Testing instrument RequestedService Condition: Ambient temperature:0~20℃±2℃ Relative humidity:≤80% Po...
Shuttle kiln for ceramic products
Shuttle kiln for ceramic products Shuttle kiln for ceramic products Brief introduction of shuttle kiln: shuttle kilnandtunnelkilnare important sintering equipment in ceramic and pro...
DC voltage test system
DC voltage test system DC voltage test system DC test systems are used to test components and complete systems found in electrical power supply systems and operating on D...
AC Series Resonant Test System
AC Series Resonant Test System AC Series Resonant Test System Applications Resonant Test Systems is appliedfor the generation ofa continuously variable alternating (AC) voltage ...
Mobile substation
Mobile substation Mobile substation Performance characteristics ① Rapid allocation: connections between equipments are connected .After connected to earth system and...
供应产品

Same products

Etong Electric Passenger Shuttle
Etong Electric Passenger Shuttle 卖方: Guang Dong Etong New Energy Technology Co., Ltd. Etong Electric Passenger Shuttle Equipmenting with a high-strength aluminum alloy chassis, elect...
Constant Velocity Joint
Constant Velocity Joint 卖方: BOYA Precision Industrial Equipments Co.,Ltd Constant Velocity Jointis the advantage product of BOYA, which is very welcomed by design institu...
Commercial ESP
Commercial ESP 卖方: KLEAN Environmental Technology Co.,Ltd Commercial ESP / 98% KL Q Plus Series Fume&mist elimination efficiency: >95% . Patented ...
Commercial ESP
Commercial ESP 卖方: KLEAN Environmental Technology Co.,Ltd Commercial ESP / 98% KL Q Plus Series Fume&mist elimination efficiency: >95% . Patented ...
ACREL AMC72L-AV3 LCD DIGITAL DISPLAY VOLTAGE METER
ACREL AMC72L-AV3 LCD DIGITAL DISPLAY VOLTAGE METER 卖方: Jiangsu Acrel Micro-grid Research&Development Institute ACREL AMC72L-AV3 LCD DIGITAL DISPLAY VOLTAGE METER Acrel's LCD digital display voltage meter is ...